4.0
BridgePoint Reader (
NON
-
FICAM
)
•
5-conductor, 22 AWG, overall shielded max distance 200 feet (or 500 feet if using 18 AWG).
•
2-conductor- twisted pair, 22 AWG max cable distance 500 feet (for Mode/Factor Control).
•
Reader will require separate power supply if the current draw is over 150 mA.
•
You must common reader P.S. ground to controller ground.
•
Ground the Drain-wire at one end only - at the DRM Board (GND).
•
Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations).
•
Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10
•
DRM Relay-2 must be use for Mode/Factor Control.
MODES/FACTORS:
•
Mode 1 Card Only (high)
•
Mode 2 Card + Pin (low)
635-DRM Terminal Functions (PN 20-0235-10)
BridgePoint Wiegand Reader
LED
(LED control line)
LED1
D 1
(Data 1)
WEG 1
VDC
(+12 VDC)
( Do not use for reader power! )
VDC
(to separate power supply)
GND
(common the Reader’s p.s. ground to the Controller ground)
GND
(common to controller ground)
D 0
(Data 0)
WEG 0
635-DRM RELAY-2
BridgePoint Mode/Factor
COM
(must tie to the reader’s power supply ground)
- -
NO
(to mode control line)
LED2
NOTES:
•
Mode signal line High (unconnected) for 1-Factor Card Only.
•
Mode signal line Low (connected to ground) for 2-Factor Card + Pin.
•
Place a schedule on Relay-2 in System Galaxy Reader Properties - to alternate Mode/Factor.