7.0

 

SCM Reader (NON-FICAM)

 

 

5-conductor, 22 AWG, overall shielded max cable distance 500 feet. 

 

2-conductor- twisted pair, 22 AWG, max cable distance 500 feet (for Mode/Factor Control). 

 

Reader will require separate power supply if the current draw is over 150 mA.  

 

You must common reader P.S. ground to controller ground.    

 

Ground the Drain-wire at one end only (at the DRM Board “GND”). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs) 

 

Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10  

 

DRM Relay-2 must be use for Mode/Factor Control.   

 

MODES/FACTORS 

 

Mode 1 Card Only 

 

Mode 2 Card + Pin 

 
 

635-DRM Terminal Functions (PN 20-0235-10) 

SCM Reader  

LED 

(LED control line) 

LED Control  

D 1 

(Data 1) 

D 1 

VDC 

(+12 VDC)   

( Do not use for reader power! )

 

VDC 

(to separate p.s.)

 

GND 

(common Reader’s p.s. ground to Controller ground) 

GND 

(common to controller ground)

 

D 0 

(Data 0) 

D 0 

 

 

635-DRM’s RELAY-2 Terminals  

SCM Mode/Factor  

COM 

(must tie to the reader’s power supply ground) 

REL 2 

NO 

(to mode control line) 

RELGRN   

 

 

NOTES: 

 

Mode signal line = High (unconnected) for 2-Factor Card + Pin. 

 

Mode signal line = Low (connected to ground) for 1-Factor Card Only 

 

Place a schedule on Relay-2 in System Galaxy Reader Properties to alternate Mode/Factor.    

 

 

 
 

Summary of Contents for 635-DRM

Page 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Page 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Page 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Page 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Page 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Page 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Page 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Page 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Page 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Page 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...

Reviews: