10.0

 

Veridt Stealth Series Reader (FICAM Solution for Technologies Industry)

 

 

5-conductor 22 AWG overall shielded; max cable distance 500 feet 

 

2-conductor Twist pair, 22 AWG, max line distance 4000 feet (RS-485 Comm. for Mode/Factor Control)  

 

A separate Power Supply is required (reader draws 400 mA at +12vdc).  

 

Must common reader's power supply ground to controller ground.    

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations). 

 

Min. Board Requirement: 635-DSI Board (Dual Serial Interface)   PN 20-0655-10   – for Mode/Factor Control 

 

READER MODES/FACTORS  

 

EWAC to 635 DRM Wiring Pinout 

Mode 1 Card Only 

 

EWAC Module 

635 DRM 

Mode 2 Card + Pin 

 

GND 

 - - - - - - - -  

GND 

Mode 3 Card + Pin + Bio 

 

D0 

 - - - - - - - -  

D0 

 

 

D1 

 - - - - - - - -  

D1 

 

 

I/O 

 - - - - - - - -  

LED 

 

 

NC 

 - - - - - - - -  

Not Used 

 

1. 

Install System Galaxy 

(SG)

 software according to Galaxy documentation. 

2. 

Validate WEB API by using address: http://localhost:8000/swagger.  

3. 

Also verify the GCS DataLoader Service is running on the Galaxy Comm/Event Server. 

4. 

When you add the 635-Series Clusters into the SG Loop/Cluster Properties screen, do the following … 

On the Advanced tab,  

set the Card Data Mode droplist to  

“Extended Card (256 Bits)”.

  

 

On the LED Options tab, set LED States: 

DOOR Locked = ‘Steady High’  
DOOR Unlocked = ‘Steady Low’

 

 

 

5. 

In the SG Reader Properties screen, configure the Reader Type field to ‘Standard Wiegand’.  

6. 

In the SG Access Group Properties screen, you must create the Access Groups you will need. 

7. 

In the SG Access Profile Properties screen, you must create 1 or more Access Profiles by assigning your access groups to 
the profile, based on your system needs.  

8. 

Install the Galaxy 635-series Controller hardware according to Galaxy documentation.  

a)  In the controller, be sure to enable 

Extended Card Mode

 (set to “yes” in lower case).  

b)  Be sure to configure the correct IP Address for the Event Server.  

9. 

Install the Technology Industries (TI) FICAM software per the manufacturer’s documentation. 

10. 

from the 

SG Cardholder screen

 perform a card lookup of the GOV. ID CARD to validate that it is correctly pushed from the 

TI FICAM Software

 into System Galaxy database. 

11. 

Install Veridt Reader and EWAC Module according to the manufacturer’s documentation.  

12. 

Connect the EWAC Module to the Galaxy Model 635 DRM (Dual Reader Module) using the wiring pinout in the table abov

e.   

 

 

Summary of Contents for 635-DRM

Page 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Page 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Page 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Page 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Page 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Page 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Page 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Page 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Page 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Page 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...