VERIDT STEALTH | NON-FICAM

 

GCS-HW-0117-SG-RDRWIR-QRG

 

www.

galaxysys

.com

 

Page 8 of 10 

 

11.0

 

Veridt Stealth Series Readers (NON-FICAM)

 

 

5-conductor 22 AWG overall shielded; max cable distance 500 feet.  

 

2-conductor Twist pair, 22 AWG, max line distance 4000 feet (RS-485 Comm. for Mode/Factor Control)  

 

Separate Power Supply required (reader draws 400 mA at +

12vdc). 

Common reader's power supply ground to controller ground.    

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations). 

 

Min. Board Requirement: 635-DRM Board (Dual Reader Module)  – PN 20-0235-10  

 

Min. Board Requirement: 635-DSI Board (Dual Serial Interface)  – PN 20-0655-10   – for Mode/Factor Control 

 

READER MODES/FACTORS  

  Mode 1 Card Only 

  Mode 2 Card + Pin 

  Mode 3 Card + Pin + Bio 

 
 

635-DRM Terminal Functions (PN 20-0235-10) 

Veridt Reader  

LED 

(LED control line) 

LED Control * required  

D 1 

(Data 1) 

DATA 1 

VDC 

(+12 VDC)   

( Do not use for reader power! )

 

VDC 

(to separate p.s.)

 

GND 

(common Reader’s p.s. ground to Controller ground) 

GND 

(common to controller ground)

 

D 0 

(Data 0) 

DATA 0 

 

 

635-DSI Terminal Functions (PN 20-0655-10) 

Veridt Reader RS-485 Comm.  

A +

 

RS-485 Data

 

 

Yellow

 Wire 

B –

 

RS-485 Data 

Blue

 Wire 

 
 

NOTES: 

 

DSI Section used for Mode/Factor Control must be set to “Veridt CAC Reader” in System Galaxy Serial Channel Properties. 

 

LED Option must be set for Door Locked “Steady High” and Door Unlocked “Steady Low” in System Galaxy Loop Properties. 

 

 

Summary of Contents for 635-DRM

Page 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Page 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Page 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Page 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Page 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Page 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Page 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Page 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Page 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Page 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...

Reviews: