Galaxy Reader Wiring QRG 

 

CONTENTS

 

 

1.0

 

Wiegand Reader – Cable Specs & Wiring Pin-out  

1

 

2.0

 

ABA Reader – Cable Specs & Wiring Pin-out 

1

 

3.0

 

Biometric Reader – General Cable Specs & Wiring 

1

 

4.0

 

BridgePoint Reader 

( NON

-

FICAM

 

)

 

2

 

5.0

 

IDEMIA (Morpho) SIGMA BIO 5G 

3

 

6.0

 

Invixium (IXM) Biometric Reader 

3

 

7.0

 

SCM Reader ( NON-FICAM ) 

4

 

8.0

 

STid Easyline Readers 

(Weigand)

 

5

 

9.0

 

STid Reader w/Galaxy Config. 

6

 

10.0

 

VERIDT 

(FICAM Solution for TI)

 

7

 

11.0

 

VERIDT Stealth Readers 

( NON-FICAM )

 

8

 

12.0

 

635-DRM Section Pinout for Reader & Relays 

9

 

13.0

 

DOOR WIRING BLOCK DIAGRAM

 

10

 

 

1.0

 

Wiegand Reader - Cable Specs & Wiring  

 

5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.   

 

Reader will require separate power supply if the current draw is over 150 mA.  

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM Terminal Functions (PN 20-0235-10) 

Wiegand Reader 

LED 

(LED control line)

 

LED Control 

D 1  

(Data 1)

 

DATA 1 

VDC 

(+12 VDC)   ( for +5 VDC use Regulator PN 92-3001-05 )

 

VDC 

GND 

(Power Supply Ground)

 

GND 

D 0 

(Data 0)

 

DATA 0 

 

2.0

 

ABA Reader - Cable Specs & Wiring 

 

 

5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.   

 

Reader will require separate power supply if the current draw is over 150 mA.  

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM Terminal Functions

 

(PN 20-0235-10) 

ABA Reader 

LED

 

(LED control line)

 

LED Control 

D 1 

 

(Data 1)

 

DATA 1 

VDC

 

(+12 VDC)   ( for +5 VDC use Regulator PN 92-3001-05 )

 

VDC 

GND

 

(Power Supply Ground)

 

GND 

D 0

 

(Data 0)

 

CLOCK 

 

3.0

 

Biometric Reader - Cable Specs & Wiring 

 

 

5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.  

 

Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet. 

 

Reader will require separate power supply if the current draw is over 150 mA.  

 

Ground the Drain-wire at one end only - at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs) 

 

See next section for information on IDEMIA Morpho Sigma Readers.

 

 

635-DRM Terminal Functions

 

(PN 20-0235-10)

 

Wiegand Reader  

LED

 

(LED control line)

 

LED Control 

D 1 

 

(Data 1)

 

DATA 1 

VDC

 

(+12 VDC)   

( Do not use for reader power! )

 

VDC 

GND

 

(Power Supply Ground)

 

GND 

D 0

 

(Data 0)

 

DATA 0 

 

    

Summary of Contents for 635-DRM

Page 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Page 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Page 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Page 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Page 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Page 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Page 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Page 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Page 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Page 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...

Reviews: