MCTB
53
The
DC power supply output
function must be selected when the output type ordered for the limit control is a
transmitter power supply.
The
Alarm output
function activates the alarm configuration settings for assigning the type of alarm logic to
apply to output 2. When the alarm condition is active, the output will turn on.
The
Limit annunciator
function uses output 2 as a means for activating an external audible alarm. When the
limit output deactivates due to the process value exceeding the high or low limit set point, output 2 will also
activate. The output will remain activate until the reset button is pressed on the Alarm screen in the runtime
application or the remote reset is activated.
4.3.13 Alarm Function
The Alarm Function is used to select the alarm type for output 2 if the output function is configured as an alarm
output. The alarm selections are mutually exclusive, i.e., selecting one will turn off the other. Once the desired
alarm type has been selected, press the “Done” button to set the alarm function for the limit control output and
return to the main Limit Configuration screen.
NOTE:
For the following alarm descriptions, PV = process value, ASP is the alarm set point and AHY is the
alarm hysteresis.
When
Process value high alarm
is selected and the process value is higher than the alarm set point (PV >
ASP), a process high alarm occurs. When the process value is lower than the alarm set point minus the alarm
hysteresis (PV < ASP
–AHY), the alarm is off.
Summary of Contents for MCTB 4.3
Page 24: ...MCTB 24...
Page 195: ...MCTB 195...
Page 227: ...MCTB 227 A 5 SmartIO Monitor Module Specifications...
Page 228: ...MCTB 228 A 6 Expansion IO Module Specifications...
Page 229: ...MCTB 229 A 7 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Page 230: ...MCTB 230...
Page 231: ...MCTB 231 Open Frame Power Supply Specifications...
Page 232: ...MCTB 232...
Page 233: ...MCTB 233 A 8 Power On Delay Relay Specifications GE1A C10HA110...
Page 234: ...MCTB 234...