Fulton Heating Solutions, Inc. -- PHW Manual -- 2010-0713
Page 19
Section 2 – Installation
1.
General Specifications and Information about Fulton Pulse Combustion
Commercial/Industrial Hydronic Boilers
Models
PHW300 PHW500 PHW750 PHW1000 PHW1400 PHW2000
BTU/HR. Input
300,000 500,000 750,000 1,000,000
1,400,000
2,000,000 NG
1,800,000 LPG
Fuel
NG/LPG NG/LPG NG/LPG NG/LPG NG/LPG NG/LPG
Approx. Dry Weight
1,395 lbs.
1,395 lbs.
2,275 lbs.
2,275 lbs.
2,970 lbs.
3,785 lbs.
Approx. Operating
Weight
1,680 lbs.
1,680 lbs.
2,625 lbs.
2,625 lbs.
3,635 lbs.
4,385 lbs.
Floor Loading
235 lbs/ft
2
235
lbs/ft
2
270
lbs/ft
2
270
lbs/ft
2
240
lbs/ft
2
250
lbs/ft
2
Power Required
120/60/1 120/60/1 120/60/1 120/60/1 120/60/1 120/60/1
Min. Required Gas
Pressure
7”W.C.NG
11” W.C. LPG
7”W.C.NG
11” W.C. LPG
7”W.C.NG
11” W.C. LPG
7”W.C.NG
11” W.C. LPG
7”W.C.NG
11” W.C. LPG
7”W.C.NG
11” W.C. LPG
Max. Amp Draw
(FLA)
4.2 4.2 4.2 4.2 4.2 10.0
MAWP
60/160 PSI
60/160 PSI
60/160 PSI
60/160 PSI
60/160 PSI
60/160 PSI
Boiler Width
27.5 IN
27.5 IN
27.5 IN
33.6 IN
33.6 IN
33.6 IN
Boiler Height
64 IN
64 IN
76 IN
76 IN
81 IN
81 IN
Boiler Depth
37.8 IN
37.8 IN
50.8 IN
50.8 IN
65 IN
75.8 IN
2. Introduction
a) The Fulton Pulse combustion hydronic boiler is an automatic gas fired, direct vent boiler.
This boiler utilizes pulse combustion principle. It requires no conventional burner controls,
no pilot and no chimney. The combustion components are of integral design with the heat
exchanger. For combustion, the boiler uses 100% outside air supplied through schedule
40 PVC pipe or can be vented conventionally. The products of combustion are vented
outdoors through non-corrosive venting materials which will withstand 480°F (249°C)
temperatures. These pipes can be routed either through a roof or through the side wall of
a building.
b) Each boiler is built to ASME and CSD-1 Codes, hydrostatically tested, test fired, and
shipped as a complete packaged unit. Gas, water, and electrical connections are similar
to conventional boilers.
c) All installations must be in accordance with the American National Standard “National
Fuel Gas Code,” latest edition, and with the requirements of local utilities or other
authorities having jurisdiction. Such applicable requirements take precedence over the
general instructions herein.
Summary of Contents for PHW 1000
Page 2: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 2...
Page 6: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 6...
Page 7: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 7 Section 1...
Page 8: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 8...
Page 17: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 17 Section 2...
Page 18: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 18...
Page 42: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 42 Figure 8...
Page 43: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 43 Figure 9 Figure 10 Figure 11...
Page 53: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 53 Section 3...
Page 54: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 54...
Page 71: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 71 Section 4...
Page 72: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 72...
Page 80: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 80...
Page 81: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 81 Section 5...
Page 82: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 82...
Page 90: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 90...
Page 92: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 92...
Page 93: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 93...