Caution
The discharge from safety relief valve shall be so arranged that there will be no danger of scalding
personnel. When the safety relief valve discharge is piped away from the boiler to the point of
discharge, there shall be provisions made for properly draining the piping.
Warning
No shutoff of any kind shall be placed between the safety relief valve and the boiler or on the
discharge pipe between such valve and the atmosphere. Doing so can cause an accidental
explosion from overpressure.
Note
The boiler, when used in conjunction with a refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium
from entering the boiler. If the boilers are connected to heating coiIs, located in air handling units
where they may be exposed to refrigerated air circulation, such boiler piping systems shall be
equipped with flow control valves or other automatic means to prevent gravity circulation of the
boiler water during the cooling cycle.
Note
See the above chart for required gas line size, based on overall Iength of pipe from meter plus
equivalent length of all fittings. Approximate sizing may be based on 1,000 BTU for 1 cubic foot of
natural gas.
Caution
Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping
thoroughly with clean water after leak check has been completed.
Warning
Do not use matches, candles, flame or other sources of ignition to check for gas Ieaks.
Note
The vent line connection on the gas pressure regulator and the low and high gas pressure
switches must be piped to outdoor air by installer in accordance with the National Fuel Gas Code,
ANSI Z223- 1-1991 or latest addenda.
In Canada gas installations must be in accordance with the current CAN/CGA B149.1 and .2 and/or
local codes.
Summary of Contents for PHW 1000
Page 2: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 2...
Page 6: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 6...
Page 7: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 7 Section 1...
Page 8: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 8...
Page 17: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 17 Section 2...
Page 18: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 18...
Page 42: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 42 Figure 8...
Page 43: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 43 Figure 9 Figure 10 Figure 11...
Page 53: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 53 Section 3...
Page 54: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 54...
Page 71: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 71 Section 4...
Page 72: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 72...
Page 80: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 80...
Page 81: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 81 Section 5...
Page 82: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 82...
Page 90: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 90...
Page 92: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 92...
Page 93: ...Fulton Heating Solutions Inc PHW Manual 2010 0713 Page 93...