Notes on Installing into the Rack
Important Notes
3.4
Notes on Installing into the Rack
V
CAUTION!
●
For safety reasons, at least two people are required to install the
system in the rack because of its weight and size.
●
Never lift the server using the handles on the front panel.
●
When connecting and disconnecting cables, observe the relevant
notes in the chapter „Important notes“ in the Technical Manual for the
corresponding rack. The Technical Manual is supplied with the corre-
sponding rack.
●
Make sure when installing the rack that the anti-tilt mechanism is
properly mounted.
●
For safety reasons, no more than one unit may be removed from the
rack at any one time during installation and maintenance work.
●
If several units are removed from the rack at the same time, there is
a risk that the rack will tilt forward.
●
The rack must be connected to the power supply by an authorized
specialist (electrician).
●
If the rack model is integrated in an installation that receives power
from an industrial (public) power supply network with the IEC309
connector, the (public) power supply protection must comply with the
requirements for non-industrial (public) power supply networks for the
type A connector.