C120-E093-04EN
11
2.2 Precautions for Installation
Table 2.4
lists the physical, electrical, and environmental specifications of the main unit.
Table 2.4 Physical, Electrical and Environmental Specifications (1/2)
Item
Specifications
Remarks
Base cabinet(*1)
(Up to 16 CPUs)
System Expansion
cabinet
(Up to 32 CPUs)
External
dimensions
Width
766 mm (30 in.)
1470 mm (58 in.)
(Total length in connection
with the Base cabinet)
Depth
1161 mm (46 in.)
1161 mm (46 in.)
Height
1800 mm (71 in.)
1800 mm (71 in.)
Weight
570 kg (1254 lb)
1140 kg (2508 lb)
(Total weight of the Base
cabinet and the System
Expansion cabinet)
Maximum weight
except the 19-inch rack
space
Power
supply
Voltage
AC 200 - 240 V
±
10%
Phase
Single
Frequency 50 / 60 Hz
Power consumption
(*2)
5700 W (At 4 SB)
4900 W (At 3 SB)
4000 W (At 2 SB)
3000 W (At 1 SB)
Approximation
(19-inch rack space is
not included.)
Heat dissipation
(*2)
20520 kJ/Hr (19449 Btu/h) (At 4 SB)
17640 kJ/Hr (16719 Btu/h) (At 3 SB)
14400 kJ/Hr (13648 Btu/h) (At 2 SB)
10800 kJ/Hr (10236 Btu/h) (At 1 SB)
Ambient
condition
(In operation)
Temperature 5 to 32
°
C (41 to 90
°
F )
Installed at altitude from 0 to 1500m (0 to 4921 ft)
5 to 28
°
C (41 to 82
°
F )
Installed at altitude from 1500 to 3000 m
(4921 to 9842 ft)
No dew condensation
Humidity
20 to 80%
Ambient
condition
(Not in
operation)
Temperature 0 to 50
°
C (32 to 122
°
F)
No altitude requirement
Connector type,
numbers
NEMA L6-30P
×
3 (
×
4)
Base cabinet = 2
19-inch rack space = 1
(19 inch = 2, when the Dual power feed
option is connected)
NEMA L6-30R
Summary of Contents for PRIMEPOWER 800
Page 1: ...Edition December 2001 PRIMEPOWER1000 800 ...
Page 5: ...PRIMEPOWER 1000 800 User s Manual C120 E093 04EN ...
Page 6: ......
Page 10: ......
Page 20: ......
Page 54: ...26 C120 E093 04EN CHAPTER 4 Hardware Overview Figure 4 4 System Board ...
Page 92: ......
Page 96: ......
Page 114: ......
Page 116: ......
Page 130: ......
Page 134: ......
Page 140: ......
Page 142: ......
Page 144: ......