1. Opening the rack door
4. Stopping the system
5. Removing the power cords
6. Replacing a faulty FRU
7. Installing the power cords
9. Performing a diagnosis test
12. Starting the system
13. Closing the rack door
Maintenance complete
2. Switching the mode switch on the operation
panel to Service mode
3. Checking the operating condition of the
system and the I/O device usage status
8. Restoring the system after replacing the
motherboard unit or PSU backplane
11. Returning the mode switch on the operation
panel to Locked mode
10. Confirming that there is no problem with the
replacement FRU
Figure
7-6
System-stopped/cold
replacement
flow
Fujitsu
M10-1/SPARC
M10-1
Service
Manual
・
June
2021
102
Summary of Contents for Oracle M10-1
Page 1: ...Fujitsu M10 1 SPARC M10 1 Service Manual Manual Code C120 E681 19EN June 2021 ...
Page 22: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 8 ...
Page 38: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 24 ...
Page 42: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 28 ...
Page 134: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 120 ...
Page 142: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 128 ...
Page 148: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 134 ...
Page 158: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 144 ...
Page 164: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 150 ...
Page 176: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 162 ...
Page 188: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 174 ...
Page 200: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 186 ...
Page 226: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 212 ...
Page 234: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 220 ...
Page 248: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 234 ...
Page 252: ...Fujitsu M10 1 SPARC M10 1 Service Manual June 2021 238 ...