External heater output
Control
Primary heater
Auxiliary heater
Function setting
Indoor unit
Wired R. C.
Control switching
external heaters
No. 61
Sensor activation*
2
Auxiliary heater
control 1
Heat pump
External device*
1
61-00
—
Auxiliary heater
control 2
Heat pump
External device
61-01
—
Heat pump prohibition
control
External device
None
61-02
On (Enabled)
Auxiliary heater
control by outdoor
temperature 1
Heat pump
External device
61-03
On (Enabled)
Auxiliary heater
control by outdoor
temperature 2
Heat Pump
External device
61-04
On (Enabled)
Auxiliary heater
control by outdoor
temperature 3
Heat Pump
External device
61-05
On (Enabled)
Auxiliary heat pump
control
External device
Heat pump
61-06
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 1
External device
Heat pump
61-07
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 2
External device
Heat pump
61-08
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 3
External device
Heat pump
61-09
On (Enabled)
NOTES:
• After turning off the heater, 3 minutes of standby time is required by next power-on of the
heater.
• For items marked “—” in the table, any of validate or invalidate of the setting are acceptable.
• *1: External device means Hot water, Electrical heater, etc.
• *2: Sensor activation:
– Setting change from the factory setting is required.
– Indoor unit fan setting will be on for safety reason without sensor activation of wired remote
controller.
Installation configuration of individual connection
External heating device is installed individually. (No use of indoor unit fan)
ON / OFF
Example of heating device:
- Floor heating device
2-4. Details of function
- (05-23) -
2. External input and output
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...