2-14. E: 65. IPM error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 65
Detective actuator
Outdoor unit
Main PCB
1. When more than normal operating current to IPM in
main PCB flows, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Outdoor fan operation failure
Outdoor heat exchanger clogged
Compressor failure
Main PCB failure
Check point 1. Check connections of outdoor unit electrical components
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 2. Check outdoor fan and heat exchanger
•
Is there anything obstructing the air distribution circuit?
•
Is there any clogging of outdoor heat exchanger?
•
Is the fan rotating by hand when operation is off?
→ If the fan motor is locked, replace it.
↓
Check point 3. Check outdoor fan
Check outdoor fan motor. (Refer to
"E: 97. Outdoor unit fan motor error (Outdoor unit)"
27.)
→ If the fan motor is failure, replace it.
↓
2-14. E: 65. IPM error (Outdoor unit)
- (03-18) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...