2-19. E: 84. Current sensor error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
8 time flash
Timer indicator
4 time flash
Economy indicator
Continuous flash
Error code
E: 84
Detective actuator
Outdoor unit
main PCB
When input current sensor has detected 0 A, while
inverter compressor is operating at higher than 56 rps,
after 1 minute upon starting the compressor. (Except
during the defrost operation)
Forecast of cause
Defective connection of electric components
External cause
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
↓
Check point 2. Check connections of outdoor
unit electrical components
Upon correcting the removed connector or mis-
wiring, reset the power.
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom,
change main PCB.
↓
End
Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
End
2-19. E: 84. Current sensor error (Outdoor unit)
- (03-24) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...