2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 11
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
than 15 seconds during normal operation.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Indoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
→ If no, go to
↓
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
→ If there is an abnormal condition, correct it by referring to the installation manual or the
DESIGN
& TECHNICAL MANUAL
.
↓
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 187 V (AC 208 V -10%) to AC 253 V (AC 230 V +10%) appears at
outdoor unit terminal L—N.
+
-
↓
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- (03-5) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUH18LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Page 36: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Page 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...