02-13
Protective Function
Detect Parts
Operating Condition
Operation
Overcurrent Break
Stop
(Compressor)
Overcurrent
Protection Circuit
COOL HEAT
Compressor stopped
Heatsink Temp
Thermistor
<Pattern starting condition>
Heat sink temperature 100°C
<Pattern reset condition>
3 minutes have elapsed and heat sink temperature 85°C
Compressor stopped
Heatsink Temp
Protection Stop
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and heat sink temperature 85°C
Compressor stopped
Error display
<Pattern starting condition>
Current value Cooling: 22.5A / Heating: 23.5A
<Pattern reset condition>
Current value Cooling: 22.5A / Heating: 23.5A
Frequency Maximum
Setting Protection
(Compressor)
<Pattern starting condition>
Current value Cooling: 23.0A / Heating: 24.0A
<Pattern reset condition>
Current value Cooling: 23.0A / Heating: 24.0A
Current Detector
Circuit
Compressor is stopped when the over currernt protectioncircuit in the
inverter PCBoad detects an abnormal current duringthe operation.
If it repeated 5 times, the compressor becomes permanentstop.
Compressor is stopped when the over current protection circuit in the
inverter PC Board detects an abnormal current at the time of start up.
Compressor becomes permanent stop if it repeated over the number
of set time.
<Reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor speed lowered
Compressor speed rise prohibited
• Pattern and start current value changed by outside
temperature
DISPLAY
E941
E931
(permanent stop)
(permanent stop)
EAC4
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......