Addresses shall be assigned to all indoor units / Signal amps.
Check for unset or duplicated addresses.
< For the setting, Refer to the page 01-06, 07 >
All the indoor units in the same refrigerant circuit shall enter the coolingtest run
state. The outdoor units corresponding to the operation capacity of the indoor
units shall operate.
< Test operation procedure, Refer to the page 01-09,10 >
Cooling
test run
All of the
indoor units
operation
(after 30 mins)
Automatic address setting
Address read
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Address
setting/
check
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
Outdoor unit push button
SW operation
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
1-2-2
Check Items After Power ON
01-04
Function setting
Are the necessary functions set ?
< For the setting, Refer to the page 01-15 18 >
Outdoor unit Main
PCB push button
SW setting/check
[Note]
Cooling test run for each refrigerant circuit.
If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot
be detected.
Judgement standard
Check
Check contents
Procedure
Power ON
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
[Note] Turn on all indoor units power in the same refrigerant circuit address.
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Indoor unit connection check
Are the number of connecting indoor units correct ?
Is the total capacity of indoor units correct ?
< For the checking, Refer to the page 01-08 >
Indoor unit
connection check
Address record
Address hold check
All the indoor units and outdoor units of the same refrigerant circuit can be
checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool
after indoor/outdoor circuit breakers were turned OFF to ON.
[Note] Before connecting service tool, the address setting has to be completed.
〜
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......