3-2 MASTER CONTROL
03-02
3-2-1 Operation Mode Control
(2) Cool, Dry and Heat Mode
Indoor fan motor
Operates according to
the AIR FLOW-MODE
setting.
See the fan control
page.
Cool
Dry
Drain pump
Turns ON-OFF by the drain pump control function
Electrical
expansion valve
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Each operation mode is controlled as below.
(1) Stop mode
Indoor fan motor
: OFF
Electric expansion valve
Drain pump
: Stop pulse
: Turns ON-OFF by the drain pump control function
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
Heat
Pulse controlled by
the temperature dif-
ference.
(
3) Priority mode
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the
connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority.
The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
Neutral
Cooling priority
Heating priority
Cooling priority
Heating priority
1. Priority mode decision methods
Method 1. (Default value)
The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating
Priority when heating depending on which operation mode (cooling, heating) was input first.
After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there
was a Stop input from all the indoor units.
Method 2. (Management by outdoor unit)
Operation mode management is made "Management by outdoor unit" by outdoor unit PUSH-SW
(field setting).
The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the outdoor
unit regardless of the current mode.
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......