En-11

6.6.  External input and external output

6.6.1  Terminal position

CN136 BLK

EXT. OUT. 1

CN137  BLU

EXT. OUT. 2

CN131

YEL

CN132 GRN

CN134    RED

CN133 WHT

CN135

ORG

EXT.  IN. 1

PLUSE.  IN

EXT.  IN. 4

EXT.  IN. 2

EXT.  IN. 3

CN115    BLK

BASE HEATER

Base heater
(CN115: Black)

Outdoor unit PC board

Input 4
(CN134: Red)

Input 3
(CN133: White)

Input 2
(CN132: Green)

Input 1
(CN131: Yellow)

Input 5 (CN135: Orange)

Output 1 (CN136: Black)

Output 2
(CN137: Blue)

 CAUTION

Do not bundle the cable for base heater with other cables.

When connecting 
cable to Input 2

Cable (for external 
input and output)

Push mount cable tie (accessory)
(tightened with transmission cable)

Push mount cable tie 
(accessory) (tightened 
with transmission 
cable)

Cable (for external input and output)
*  If the outdoor unit is not installed in the wall, cover the exposed 

part of cable with a 0.039 in (1 mm) thick or more insulation tubing.

6.6.2  External input terminal

Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation 
peak control setting, emergency/batch stop and electricity meter pulse are possible from 
the outside.

Wiring method and specifications

*  A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is 

150 m.

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed

*  For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.

Connected unit Connected unit Connected unit Connected unit Connected unit

Input 1
CN131 
(Yellow)

Input 2
CN132 
(Green)

Input 3
CN133 
(White)

Input 4
CN134 
(Red)

Input 5
CN135 
(Orange)

P.C.B

Operation behavior

Each input terminal works as follows.

Connector

Input signal

Status

Input 1
CN131 (Yellow)

OFF

Normal operation

ON

Low noise mode operation

Input 2
CN132 (Green) *1

OFF

Cooling priority

ON

Heating priority

Input 3
CN133 (White)

OFF

Normal operation

ON

Outdoor unit operation peak control

Input 4
CN134 (Red)

OFF

Normal operation

ON

Batch stop or Emergency stop operation *2, *3

Input 5
CN135 (Orange) *4

No pulse

No information from electricity meter

Pulse

Power usage information from electricity meter

The operations of each input terminal and the selection of function are set with the push 
button on the PC board of outdoor unit. About the setting, please refer to “7.4. Push button 
setting”.

NOTES:

*1:  The “external input priority mode” must be set by pressing push button on PC board 

of outdoor unit. (Refer to “7. FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7. FIELD SETTING”.)

*3:  The emergency stop function mounted in this model does not guarantee the regula-

tions of each country. For this reason, sufficient checking is necessary regarding 
use. 
Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication 
line, communication error due to noise, VRF external input circuit trouble, etc. must 
be considered, the provision of double measures that add direct interruption of the 
power supply by switch, etc. is recommended as a precaution.

*4:  Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or 

more.

6.6.3  External output terminal

You can detect the operation condition of outdoor unit and the abnormal situation of both 
indoor and outdoor unit.
Wiring method and specifications

Error status

This output indicates the outdoor unit 
and connected indoor unit's “Normal” or 
“Error” status.

Operation status

This output indicates the outdoor unit's 
“Operation” status.

Connector

Output 

voltage

Status

Output 1
CN136 
(Black)

0V

Normal

DC 12-24 V 

*5

Error

Output 2
CN137 
(Blue)

0V

Stop

DC 12-24 V 

*5

Operation

P.C.B

CN136 (Black) or 
CN137 (Blue)

DC power supply 
(External) 12-24 V

Connected load (Operation Indica-
tor or Error Indicator)

Connected unit

*5:  Provide a DC 12 to 24 V power supply. 

Select a power supply capacity with an ample surplus for the connected load.

*6:  The allowable current is 30 mA or less. 

Provide a load resistance such that the current becomes 30 mA or less.

*7:  Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.

Do not impress a voltage exceeding 24 V across pins 1-2.

*  A twisted pair cable (22 AWG (0.33 mm²)) should be used. 

Maximum length of cable is 492 ft (150 m).

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

6.6.4  Base heater terminal

This is the output signal for base heater. Output signal ON, when the outdoor temperature 
goes down below 36 °F (2 °C), and signal OFF at the outdoor temperature 39 °F (4 °C).

  

Voltage: 
power supply input voltage

cable

(18AWG (0.82mm²))

P.C.B.

Base heater *9

CN115 

(Black)

*8

*8:  Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
*9:  The allowable current is 1 A or less.

9380545309-02.indb   11

9380545309-02.indb   11

2018/12/27   8:39:05

2018/12/27   8:39:05

Summary of Contents for Airstage AOU120RLAVL

Page 1: ...T UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado PART No 9380545309 02 AOU72RLAVL AOU96RLAVL AOU120RLAVL 9380545309 02 indb i 9380545309 02 indb i 2018 12 27 8 38 58 2018 12 27 8 38 58 ...

Page 2: ...to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip pi...

Page 3: ...rical Code by authorized personnel only Cancer and Reproductive Harm www P65Warnings ca gov CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instruc...

Page 4: ...CN135 UTY XWZXZ9 For External output Base heater CN115 2 6 About unit of the length All Fujitsu General products are manufactured to metric units and tolerances United States customary units are provided for reference only In cases where exact dimensions and tolerances are required always refer to metric units 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the locati...

Page 5: ...space If you are installing more outdoor units than indicated here please ensure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Keep the space shown in the ...

Page 6: ...snow hoods and drift prevention fencing is recommended when blowing and drifting snow is common to the region 3 3 3 Outdoor units installation in multi row The following settings are not recommended in case of cooling by a low outside tem perature Unit in mm 1 Single parallel unit arrangement 2 Multiple parallel unit arrangement 4 100 or more 24 600 or more 40 1000 or more 79 2000 or more 20 500 o...

Page 7: ...or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm 2 Allowable tensile stress 61 N mm 3 Endurance pressure of the pipes 609 psi 4 2 MPa Table B Diameter of piping used between outdoor unit and first separation tube or header For the following installation conditions it is necessary to increase the piping size Condition 1 Total indoor unit ca...

Page 8: ...t bend or stretch the pipes more than 3 times 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance Pressure regulating valve Cap Nitrogen gas Brazing area Apply nitrogen gas while brazing the pipes Nitrogen gas...

Page 9: ...ase comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord securely to the terminal Faulty installation can ca...

Page 10: ...he exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may lead to an open circuit and a communication error Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cr...

Page 11: ...n the figure below Tightening torque lbf ft N m M3 screw 4 4 to 5 3 0 5 to 0 6 M5 screw 17 7 to 26 5 2 0 to 3 0 Power supply terminal Ring terminal M5 Transmission terminal M3 Power supply cable Conduit Power supply cable Transmission cable Transmission cable Push mount cable tie accessories Push mount cable tie accessories Earth ground cable 5 16 to 3 8 in 8 to 10 mm 1 to 1 9 16 in 25 to 40 mm Ho...

Page 12: ... priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking is necessary regarding use Especially s...

Page 13: ...the wired remote controller 22 Forbidden Factory default 2 2 0 0 z 23 Forbidden Factory default 2 3 0 0 z 24 Forbidden Factory default 2 4 0 0 z 25 Forbidden Factory default 2 5 0 0 z 26 Forbidden Factory default 2 6 0 0 z 27 Forbidden Factory default 2 7 0 0 z 28 Change of unit Temperature Celsius C 2 8 0 0 z Fahrenheit F 0 1 7 FIELD SETTING CAUTION Discharge the static electricity from your body...

Page 14: ...l automatically return to the low noise mode 41 Low noise mode setting 1 Off Normal 4 1 0 0 z On Low noise mode 0 1 42 Low noise mode level setting Level 1 4 2 0 0 z Level 2 0 1 Forbidden 0 2 50 Forbidden Factory default 5 0 0 0 z 51 Forbidden Factory default 5 1 0 0 z 52 Forbidden Factory default 5 2 0 0 z 60 Forbidden Factory default 6 0 0 0 z 61 Forbidden Factory default 6 1 0 0 z 64 Forbidden ...

Page 15: ...plifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the ins...

Page 16: ...valve Blank cap 72 96 120 6 0 to 7 3 8 1 to 9 9 13 3 to 16 2 18 0 to 22 0 19 9 to 24 4 27 0 to 33 0 16 6 to 20 3 22 5 to 27 5 8 4 to 10 3 11 4 to 14 0 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It can rupture th...

Page 17: ...lated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lbs kg AOU72RLAVL 24 25 11 0 AOU96RLAVL 24 25 11 0 AOU120RLAVL 24 25 11 0 Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m Ø 1 4 6 35 0 014 0 021 Ø 3 8 9 52 0 039 0 058 Ø 1 2 12 70 0 077 0 114 Ø 5 8 15 88 0 120 0 178 Ø 3 4 19 05 0 180 0 268 1 Calculation of ad...

Page 18: ... temperature control will not activate during test opera tion continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operatio...

Page 19: ... 4 2 Outdoor unit network communication 2 error E 1 4 5 The number of indoor unit shortage Function setting error E 2 2 1 Indoor unit capacity error E 2 4 2 Connection unit number error Indoor unit E 2 6 1 Indoor unit duplicate address error E 2 8 1 Auto address setting error E 2 8 4 Signal amplifier auto address error Indoor unit actuator error E 5 U 1 Indoor unit miscellaneous error Outdoor unit...

Reviews: