background image

En-9

6.2.  Knockout hole

 CAUTION

Be careful not to deform or scratch the panel while opening the knockout holes.

After opening the knockout hole, remove the burr on the edges to prevent snapping of 
cables.
It is recommended to apply rust proof paint on the edges to prevent rust.

Knockout holes are provided in front and lateral sides for wiring.

Unit: in (mm)

Ø 1-3/8
(34.5)

Ø 1-3/8

(34.5)

Ø 7/8
(22.2)

Ø 7/8

(22.2)

6.3.  Selecting power supply cable and breaker

CAUTION

Obtain the distribution network operator's agreement about the power capacity of the 
power supply system and specifi cation of the cable. when you connect the outdoor unit 
with the power supply.

Regulation of wire size and circuit breaker diff ers from each locality, please refer in ac-
cordance with local rules.

•  Select the power cable type and size in accordance with relevant local and national regu-

lations.

•  Make sure the specifi cations for local wiring power cable and branch wiring are in compli-

ance with local code.

•  Select the correct cable type and size according to the country or region’s regulations.
•  Use copper conductors only.
•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is longer.

Selecting power supply cable and breaker when connecting single outdoor unit.
Refer to the table for the breaker specifi cations of each installation condition.

Model

MCA

MAX. CKT. BKR

GFEB

AOU72RLAVL

38 A

40 A

100 mA 

0.1 sec or less

AOU96RLAVL

39 A

AOU120RLAVL

47 A

50 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR: Maximum Circuit Breaker
•  Select the appropriate breaker of the described specifi cation according to the national or 

regional standards.

•  Select the breaker that enough load current can pass through it.

In case of connected outdoor unit

Breaker 1: Ground Fault Equipment Breaker (GFEB)
Breaker 2: Maximum Circuit Breaker (MAX. CKT. BKR)

GOOD

Transmission cable

Remote controller cable

208/230 V 

3ø 60 Hz

Breaker 1

208/230 V 1ø 60 Hz

Outdoor unit power 

supply cable

Indoor unit 
power supply 
cable

Breaker 2

Breaker 1
Breaker 2

6.4.  Transmission line

 CAUTION

Caution when wiring cable:
When stripping off the coating of lead wire, always use the exclusive tool such as a 
wire stripper. If there is no exclusive tool available necessarily, carefully strip the coat-
ing by a cutter etc. so that the conductive wire is not damaged.
If it is damaged, it may lead to an open circuit and a communication error.

Pay attention to the following points while attaching wires on the terminal board.
• Do not attach 2 wires on one side.
• Do not twist wires.
• Do not cross the wires.
• Do not shorted at edge at root.

GOOD

PROHIBITED

1 wire

2 pcs at one side

Wires twisted

2 wires

Shorted at edge

Shorted at root

6.4.1  Transmission wiring specifi cations

Follow the specifications below for the transmission cable.

Use

Size

Cable type

Remarks

Transmission cable

22 AWG

(0.33 mm²)

LEVEL 4 (NEMA) non-polar 
2 core, twisted, shielded pair, 
solid core, diameter 0.026 in 
(0.65 mm)

LONWORKS ® 
compatible cable

Twisted pair with shielded type.
Use the shielded wire specified and always ground it both end.

6.4.2  Wiring rules

(1) Total length of transmission cable

Total transmission line length: MAX 11,811 ft (3,600 m)

EF + EG + GH + HJ + HK + KL < 11,811 ft (3,600 m) (Fig.2)

In the following cases, Signal Amplifier is required.

1)

When the total length of the transmission line exceeded 1,640 ft (500 m).
AB + BC + BD > 1,640 ft (500 m) (Fig.1)

2)

When the total number of units* is over 64.

3)

Transmission line length between each unit* ≥ 1,312 ft (400 m)

(2) Length of transmission cable between 1 network segment (NS)

EF + EG + GH + HJ + HK ≤ 1,640 ft (500 m) (Fig.2)
KL ≤ 1,312 ft (400 m) (Fig.2)

Unit* means indoor unit, outdoor unit, Touch Panel Controller and System Controller, 
Signal Amplifier, single split adaptor, Network Convertor etc.

Fig. 1

Transmission line

System 
controller

Touch panel 
controller

When AB + BC + BD > 1,640 ft (500 m)
: Signal Amplifier is required.

Outdoor unit

Indoor unit

Terminal resistor

Fig. 2

Outdoor unit

Indoor unit

Signal Amplifier

System 
Controller

Touch 
Panel 
Controller

Transmission line

Terminal resistor

Terminal resistor

NS 1

NS 2

NOTES:

Do not use loop wiring. This 
may lead to parts damage and 
erroneous operation.

6.4.3  Enabling/Disabling automatic address setting

You can enable/disable automatic address setting for the indoor unit and the signal ampli-
fier.
To enable automatic address setting for the indoor unit, connect the indoor unit to outdoor 
units under the same refrigerant system.

9380545309-02.indb   9

9380545309-02.indb   9

2018/12/27   8:39:01

2018/12/27   8:39:01

Summary of Contents for Airstage AOU120RLAVL

Page 1: ...T UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado PART No 9380545309 02 AOU72RLAVL AOU96RLAVL AOU120RLAVL 9380545309 02 indb i 9380545309 02 indb i 2018 12 27 8 38 58 2018 12 27 8 38 58 ...

Page 2: ...to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip pi...

Page 3: ...rical Code by authorized personnel only Cancer and Reproductive Harm www P65Warnings ca gov CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instruc...

Page 4: ...CN135 UTY XWZXZ9 For External output Base heater CN115 2 6 About unit of the length All Fujitsu General products are manufactured to metric units and tolerances United States customary units are provided for reference only In cases where exact dimensions and tolerances are required always refer to metric units 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the locati...

Page 5: ...space If you are installing more outdoor units than indicated here please ensure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Keep the space shown in the ...

Page 6: ...snow hoods and drift prevention fencing is recommended when blowing and drifting snow is common to the region 3 3 3 Outdoor units installation in multi row The following settings are not recommended in case of cooling by a low outside tem perature Unit in mm 1 Single parallel unit arrangement 2 Multiple parallel unit arrangement 4 100 or more 24 600 or more 40 1000 or more 79 2000 or more 20 500 o...

Page 7: ...or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm 2 Allowable tensile stress 61 N mm 3 Endurance pressure of the pipes 609 psi 4 2 MPa Table B Diameter of piping used between outdoor unit and first separation tube or header For the following installation conditions it is necessary to increase the piping size Condition 1 Total indoor unit ca...

Page 8: ...t bend or stretch the pipes more than 3 times 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance Pressure regulating valve Cap Nitrogen gas Brazing area Apply nitrogen gas while brazing the pipes Nitrogen gas...

Page 9: ...ase comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord securely to the terminal Faulty installation can ca...

Page 10: ...he exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may lead to an open circuit and a communication error Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cr...

Page 11: ...n the figure below Tightening torque lbf ft N m M3 screw 4 4 to 5 3 0 5 to 0 6 M5 screw 17 7 to 26 5 2 0 to 3 0 Power supply terminal Ring terminal M5 Transmission terminal M3 Power supply cable Conduit Power supply cable Transmission cable Transmission cable Push mount cable tie accessories Push mount cable tie accessories Earth ground cable 5 16 to 3 8 in 8 to 10 mm 1 to 1 9 16 in 25 to 40 mm Ho...

Page 12: ... priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking is necessary regarding use Especially s...

Page 13: ...the wired remote controller 22 Forbidden Factory default 2 2 0 0 z 23 Forbidden Factory default 2 3 0 0 z 24 Forbidden Factory default 2 4 0 0 z 25 Forbidden Factory default 2 5 0 0 z 26 Forbidden Factory default 2 6 0 0 z 27 Forbidden Factory default 2 7 0 0 z 28 Change of unit Temperature Celsius C 2 8 0 0 z Fahrenheit F 0 1 7 FIELD SETTING CAUTION Discharge the static electricity from your body...

Page 14: ...l automatically return to the low noise mode 41 Low noise mode setting 1 Off Normal 4 1 0 0 z On Low noise mode 0 1 42 Low noise mode level setting Level 1 4 2 0 0 z Level 2 0 1 Forbidden 0 2 50 Forbidden Factory default 5 0 0 0 z 51 Forbidden Factory default 5 1 0 0 z 52 Forbidden Factory default 5 2 0 0 z 60 Forbidden Factory default 6 0 0 0 z 61 Forbidden Factory default 6 1 0 0 z 64 Forbidden ...

Page 15: ...plifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the ins...

Page 16: ...valve Blank cap 72 96 120 6 0 to 7 3 8 1 to 9 9 13 3 to 16 2 18 0 to 22 0 19 9 to 24 4 27 0 to 33 0 16 6 to 20 3 22 5 to 27 5 8 4 to 10 3 11 4 to 14 0 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It can rupture th...

Page 17: ...lated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lbs kg AOU72RLAVL 24 25 11 0 AOU96RLAVL 24 25 11 0 AOU120RLAVL 24 25 11 0 Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m Ø 1 4 6 35 0 014 0 021 Ø 3 8 9 52 0 039 0 058 Ø 1 2 12 70 0 077 0 114 Ø 5 8 15 88 0 120 0 178 Ø 3 4 19 05 0 180 0 268 1 Calculation of ad...

Page 18: ... temperature control will not activate during test opera tion continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operatio...

Page 19: ... 4 2 Outdoor unit network communication 2 error E 1 4 5 The number of indoor unit shortage Function setting error E 2 2 1 Indoor unit capacity error E 2 4 2 Connection unit number error Indoor unit E 2 6 1 Indoor unit duplicate address error E 2 8 1 Auto address setting error E 2 8 4 Signal amplifier auto address error Indoor unit actuator error E 5 U 1 Indoor unit miscellaneous error Outdoor unit...

Reviews: