En-13
29
Change of unit
(Pressure)
Mpa
2
9
0
0
z
psi
0
1
30
Energy saving
level setting *1
Level 1 (stop)
3
0
0
0
z
Level 2
(operated at 40% capacity)
0
1
Level 3
(operated at 60% capacity)
0
2
Level 4
(operated at 80% capacity)
0
3
Level 5
(operated at 100% capacity)
0
4
The capacity limit can be selected by the external input terminal (CN133) when operat-
ing with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating perfor-
mance will also drop.
31
Forbidden (Factory default)
3
1
0
0
z
34
Forbidden (Factory default)
3
4
0
0
z
35
Presence of
heater selection
control using
outdoor tempera-
ture *1
Disable
3
5
0
0
z
Enable
0
1
If “Heater selection control 1 or 2 using outdoor temperature” is used for any of the
indoor units of the refrigerant system, select "Valid". For more details on settings for this
item, see the Design & Technical Manual.
36
Outdoor tempera-
ture zone bound-
ary temperature
A *1
-4.0°F (-20°C)
3
6
0
0
z
-0.4°F (-18°C)
0
1
3.2°F (-16°C)
0
2
6.8°F (-14°C)
0
3
10.4°F (-12°C)
0
4
14.0°F (-10°C)
0
5
17.6°F (-8°C)
0
6
21.2°F (-6°C)
0
7
24.8°F (-4°C)
0
8
For more details on settings for this item, see the Design & Technical Manual.
37
Outdoor tempera-
ture zone bound-
ary temperature
B *1
42.8°F (6°C)
3
7
0
0
z
14.0°F (-10°C)
0
1
17.6°F (-8°C)
0
2
21.2°F (-6°C)
0
3
24.8°F (-4°C)
0
4
28.4°F (-2°C)
0
5
32.0°F (0°C)
0
6
35.6°F (2°C)
0
7
39.2°F (4°C)
0
8
42.8°F (6°C)
0
9
46.4°F (8°C)
1
0
50.0°F (10°C)
1
1
53.6°F (12°C)
1
2
57.2°F (14°C)
1
3
60.8°F (16°C)
1
4
64.4°F (18°C)
1
5
For more details on settings for this item, see the Design & Technical Manual.
38
Forbidden (Factory default)
3
8
0
0
z
40
Capacity prior-
ity setting (in low
noise mode) *1
Off (quiet priority)
4
0
0
0
z
On (capacity priority)
0
1
If the cooling/heating performance becomes insufficient when the low noise mode is set, it is
possible to set “capacity priority” that automatically cancels the low noise mode (once perfor-
mance is restored, the mode will automatically return to the low noise mode).
41
Low noise mode
setting *1
Off (Normal)
4
1
0
0
z
On (Low noise mode)
0
1
42
Low noise mode
level setting
Level 1
4
2
0
0
z
Level 2
0
1
Forbidden
0
2
50
Forbidden (Factory default)
5
0
0
0
z
51
Forbidden (Factory default)
5
1
0
0
z
52
Forbidden (Factory default)
5
2
0
0
z
60
Forbidden (Factory default)
6
0
0
0
z
61
Forbidden (Factory default)
6
1
0
0
z
64
Forbidden (Factory default)
6
4
0
0
z
70
Electricity meter
No. setting 1 *2
Setting number (x00)
7
0
0
0
z
Setting number (x01)
0
1
······
···
···
Setting number (x98)
9
8
Setting number (x99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.
71
Electricity meter
No. setting 2 *2
Setting number (0xx)
7
1
0
0
z
Setting number (1xx)
0
1
Setting number (2xx)
0
2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting 1 *3
Setting number (xx00)
7
2
0
0
z
Setting number (xx01)
0
1
······
···
···
Setting number (xx98)
9
8
Setting number (xx99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting con-
nected to CN135.
73
Electricity meter
pulse setting 2 *3
Setting number (00xx)
7
3
0
0
z
Setting number (01xx)
0
1
······
···
···
Setting number (98xx)
9
8
Setting number (99xx)
9
9
Set the hundreds digit and thousands digit of the electricity meter pulse setting con-
nected to CN135.
80
Forbidden (Factory default)
8
0
0
0
z
81
Forbidden (Factory default)
8
1
0
0
z
82
Forbidden (Factory default)
8
2
0
0
z
83
Forbidden (Factory default)
8
3
0
0
z
84
Forbidden (Factory default)
8
4
0
0
z
85
Forbidden (Factory default)
8
5
0
0
z
86
Forbidden (Factory default)
8
6
0
0
z
87
Forbidden (Factory default)
8
7
0
0
z
90
Forbidden (Factory default)
9
0
0
0
z
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
9380545309-02.indb 13
9380545309-02.indb 13
2018/12/27 8:39:06
2018/12/27 8:39:06