En-10
Example: Disable Automatic Address setting
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Transmission line
Transmission line
Transmission line
Example: Enable Automatic Address setting
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Transmission line
Transmission line
Transmission line
6.5. Wiring method
6.5.1 Connection diagrams
L1 L2 L3
L1 L2 L3
Breaker 1: Ground Fault Equipment
Breaker (GFEB)
Breaker 2: Maximum Circuit Breaker
(MAX. CKT. BKR)
Power supply
208/230V 3~ 60Hz
To other refrigerant circuit
outdoor unit
Outdoor unit
Transmission
Transmission
Transmission
Transmission
Transmission
Power supply
Remote control
Remote control
Remote control
Power supply
Power supply
Power supply
Indoor unit
Power supply
208/230V ~ 60Hz
Remote
controller
*1
*1
*1
Remote
controller
Remote
controller
Power supply
208/230V ~ 60Hz
Power supply
208/230V ~ 60Hz
Indoor unit
Indoor unit
Breaker 1
Breaker 1
Breaker 1
Breaker 1
Breaker 2
Breaker 2
Breaker 2
Breaker 2
*1: The number of power supply terminals is different depending on the indoor unit
model. For the wiring, refer to the indoor unit installation manual.
• There are two types of remote controller: the 2-wire type and the 3-wire type. For details,
see the relevant remote controller installation manual. (When connecting the 2-wire type
remote controller, Y3 is not used.)
The wiring example for outdoor and indoor units is shown in figure.
6.5.2 Wiring procedure
• Remove the service panel. And connect the cable to the terminal in accordance with the
terminal name plate.
• Use a ring terminal to connect the electric cables to the power supply terminal board.
• Keep the earth cable longer than the other cables.
• After connecting the electric cable, secure them with a cable clamp.
• Connect the cable without applying excessive tension.
• Use the specified cable type and connect the cable securely.
Secure with a cable
clamp as shown in the
figure below.
Tightening torque
[lbf·ft (N·m)]
M3 screw
4.4 to 5.3 (0.5 to 0.6)
M5 screw
17.7 to 26.5 (2.0 to 3.0)
Power supply terminal
Ring
terminal
(M5)
Transmission terminal (M3)
Power supply cable
Conduit
Power supply
cable
Transmission cable
Transmission
cable
Push mount
cable tie
(accessories)
Push mount cable tie
(accessories)
Earth
(ground)
cable
5/16 to 3/8 in
(8 to 10 mm)
1 to 1-9/16 in
(25 to 40 mm)
How to connect wiring to the terminal
Caution when wiring cable
(1) Use ring terminals with insulating sleeves as shown in the figure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that
the cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Strip 3/8 in
(10 mm)
Cable
Screw with
special washer
Ring terminal
Terminal block
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
Shielding the transmission cable
Connect both ends of the shielded
wire of the transmission cable to
the earth (ground) terminal of the
equipment or to the earth (ground)
screw near the terminal.
Be sure to use one side of a twisted
pair cable when using transmission
cable with 2 sets of twisted pair
cables.
Wind with insulation tape to prevent short circuit
Use one side
of the twisted
pair cable
Connect both ends of shielded
wire to earth (Ground).
Attaching the conduit
Front connection
Cable (with
conduit)
lock nut
Lateral connection
• Fix the conduit with the supporters as shown below.
Supporter
Conduit (Power supply cable)
Outdoor unit
30 in
(756 mm)
or less
54 in
(1,361 mm)
or less
54 in
(1,361 mm)
or less
54 in
(1,361 mm)
or less
9380545309-02.indb 10
9380545309-02.indb 10
2018/12/27 8:39:02
2018/12/27 8:39:02