En-17

9.1.3  Error displays

• When error occurs, “Err” and “Number of errors occurred” are alternately displayed on 

the 7-segment display every 1 second.

• For the content of error, please refer to the “10.2. Error codes”.
• When error codes are displayed, all the error codes can be confirmed by pressing the 

“SELECT” button.

Example:

When “Indoor unit capacity error [E221]” and “Indoor unit duplicate address error [E261]” 
occurred.

(*1)  When the address of the overlap indoor unit is 

displayed, press and hold the “ENTER” button 
for more than 3 seconds.

(*2)  When errors other than the address of the 

overlap indoor unit exist, press “SELECT” but-
ton to switch to the next error.

If error occurs, it will display “-”.

[Ad + address number]

9.2.  Pre-check for test run

Before the test operation, check the following items.
(1)  Is there a gas leakage? (At pipe connections {flange connections and brazed areas})
(2)  Is the system charged with the specified volume of refrigerant?
(3)  Is the refrigerant circuit address correct?
(4)  Is a breaker installed at the power supply cable of outdoor unit?
(5)  Are the cable connected to the terminals without looseness, and in accordance with 

the specifications?

(6)  Are the initial settings of the switches of the outdoor unit correctly configured?
(7)  Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe)
(8)  Is power supplied to the crank case heater for more than 12 hours? Electricity current 

in short period of time may result in compressor damage.

(9)  Are all the indoor units within the same coolant system connected to the power? Op-

erating indoor units which are not connected to the power may result in malfunctions.

(10)  Is Indoor unit connection check performed? Test run doesn't operate if Indoor unit 

connection check is not performed.

After checking that the above items are all in order, refer to 
“9.3. Test run method” to test operation the unit.
If there are problems, adjust immediately and recheck.

9.3.   Test run method

Be sure to configure test run settings only when the outdoor unit has stopped operating.

• Depending on the communication status between the indoor and outdoor units, it may 

take several minutes for the system to start operating after settings for the test run are 
complete.

• After the test run settings are complete, the outdoor unit and the connected indoor 

units will start operating. Room temperature control will not activate during test opera-
tion (continuous operation).

• If a knocking sound can be heard in the liquid compression of the compressor, stop 

the unit immediately and then energize the crank case heater for a sufficient length of 
time before restarting the operation.

Perform test operation for each refrigerant system.
You can set “cooling test operation" or “heating test operation” with the push button on the 
outdoor unit PC board.

9.  TEST RUN

9.1.  Indoor unit connection check

Normal operation will not be possible without performing the Indoor unit connection check.

9.1.1  Things to confi rm before starting the Indoor unit connection 

check

To ensure safety, check that the following work, inspections and operations have been 
completed.

Check Item

Check Column

1

Check that all work on the wiring connecting the outdoor 
unit and indoor units  has been completed.

2

Is a breaker installed at the power supply cable of out-
door unit and every indoor units?

3

Are the cables connected to the terminals without loose-
ness, and in accordance with the specifications?

4

Are all the indoor units stopped? Indoor unit connection 
check cannot be performed if any unit is operating.

5

Is the connection to Service tool (UTY-ASGX) and Web 
monitoring tool (UTY-AMGX) stopped?

9.1.2  Operating procedure for Indoor unit connection check

Please perform the indoor unit connection check according to following procedures.
The Indoor unit connection check can be completed within several minutes.

Set to Function mode [F3].

(When [F4] to [F9] are displayed, continue to press 
the “SELECT” button until [F3] is displayed.)

Press the “SELECT” button until “12” is displayed.

When indoor unit connection 
check cannot be performed

Turn on the power of indoor 
unit and outdoor unit.

Press the “ENTER” button for more than 3 seconds.

This will be displayed when the Indoor unit connection 
check starts.

: Press the “MODE/EXIT” button

: Press the “SELECT” button

: Press the “ENTER” button.
: Press the “ENTER” button for 

more than 3 seconds.

(*1) The number of connected indoor units

Ex.) When 8 units are connected

(*2) Volume ratio of the indoor units connection

Ex.) When the ratio is 120%

Please refer to the following “Error displays” 
for details.

When it finishes normally, nothing will be displayed on 
7-segment display. 

When error occurs

Confirm the number of connected indoor units and the 
volume ratio of the indoor units connection.

Exit indoor unit connection check mode.

9380545309-02.indb   17

9380545309-02.indb   17

2018/12/27   8:39:07

2018/12/27   8:39:07

Summary of Contents for Airstage AOU120RLAVL

Page 1: ...T UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado PART No 9380545309 02 AOU72RLAVL AOU96RLAVL AOU120RLAVL 9380545309 02 indb i 9380545309 02 indb i 2018 12 27 8 38 58 2018 12 27 8 38 58 ...

Page 2: ...to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip pi...

Page 3: ...rical Code by authorized personnel only Cancer and Reproductive Harm www P65Warnings ca gov CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instruc...

Page 4: ...CN135 UTY XWZXZ9 For External output Base heater CN115 2 6 About unit of the length All Fujitsu General products are manufactured to metric units and tolerances United States customary units are provided for reference only In cases where exact dimensions and tolerances are required always refer to metric units 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the locati...

Page 5: ...space If you are installing more outdoor units than indicated here please ensure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Keep the space shown in the ...

Page 6: ...snow hoods and drift prevention fencing is recommended when blowing and drifting snow is common to the region 3 3 3 Outdoor units installation in multi row The following settings are not recommended in case of cooling by a low outside tem perature Unit in mm 1 Single parallel unit arrangement 2 Multiple parallel unit arrangement 4 100 or more 24 600 or more 40 1000 or more 79 2000 or more 20 500 o...

Page 7: ...or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm 2 Allowable tensile stress 61 N mm 3 Endurance pressure of the pipes 609 psi 4 2 MPa Table B Diameter of piping used between outdoor unit and first separation tube or header For the following installation conditions it is necessary to increase the piping size Condition 1 Total indoor unit ca...

Page 8: ...t bend or stretch the pipes more than 3 times 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance Pressure regulating valve Cap Nitrogen gas Brazing area Apply nitrogen gas while brazing the pipes Nitrogen gas...

Page 9: ...ase comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord securely to the terminal Faulty installation can ca...

Page 10: ...he exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may lead to an open circuit and a communication error Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cr...

Page 11: ...n the figure below Tightening torque lbf ft N m M3 screw 4 4 to 5 3 0 5 to 0 6 M5 screw 17 7 to 26 5 2 0 to 3 0 Power supply terminal Ring terminal M5 Transmission terminal M3 Power supply cable Conduit Power supply cable Transmission cable Transmission cable Push mount cable tie accessories Push mount cable tie accessories Earth ground cable 5 16 to 3 8 in 8 to 10 mm 1 to 1 9 16 in 25 to 40 mm Ho...

Page 12: ... priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking is necessary regarding use Especially s...

Page 13: ...the wired remote controller 22 Forbidden Factory default 2 2 0 0 z 23 Forbidden Factory default 2 3 0 0 z 24 Forbidden Factory default 2 4 0 0 z 25 Forbidden Factory default 2 5 0 0 z 26 Forbidden Factory default 2 6 0 0 z 27 Forbidden Factory default 2 7 0 0 z 28 Change of unit Temperature Celsius C 2 8 0 0 z Fahrenheit F 0 1 7 FIELD SETTING CAUTION Discharge the static electricity from your body...

Page 14: ...l automatically return to the low noise mode 41 Low noise mode setting 1 Off Normal 4 1 0 0 z On Low noise mode 0 1 42 Low noise mode level setting Level 1 4 2 0 0 z Level 2 0 1 Forbidden 0 2 50 Forbidden Factory default 5 0 0 0 z 51 Forbidden Factory default 5 1 0 0 z 52 Forbidden Factory default 5 2 0 0 z 60 Forbidden Factory default 6 0 0 0 z 61 Forbidden Factory default 6 1 0 0 z 64 Forbidden ...

Page 15: ...plifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the ins...

Page 16: ...valve Blank cap 72 96 120 6 0 to 7 3 8 1 to 9 9 13 3 to 16 2 18 0 to 22 0 19 9 to 24 4 27 0 to 33 0 16 6 to 20 3 22 5 to 27 5 8 4 to 10 3 11 4 to 14 0 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It can rupture th...

Page 17: ...lated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lbs kg AOU72RLAVL 24 25 11 0 AOU96RLAVL 24 25 11 0 AOU120RLAVL 24 25 11 0 Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m Ø 1 4 6 35 0 014 0 021 Ø 3 8 9 52 0 039 0 058 Ø 1 2 12 70 0 077 0 114 Ø 5 8 15 88 0 120 0 178 Ø 3 4 19 05 0 180 0 268 1 Calculation of ad...

Page 18: ... temperature control will not activate during test opera tion continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operatio...

Page 19: ... 4 2 Outdoor unit network communication 2 error E 1 4 5 The number of indoor unit shortage Function setting error E 2 2 1 Indoor unit capacity error E 2 4 2 Connection unit number error Indoor unit E 2 6 1 Indoor unit duplicate address error E 2 8 1 Auto address setting error E 2 8 4 Signal amplifier auto address error Indoor unit actuator error E 5 U 1 Indoor unit miscellaneous error Outdoor unit...

Reviews: