5-1 COMPRESSOR OPERATION CONTROL
5. OUTDOOR UNIT OPERATION CONTROL
5-1-1 OPERATION STOP CONDITION
Compressor operation condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same
refrigerant system is input, the compressor operates.
But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation
During compressor recovery operation
During deicing operation
Failure ( except for a part )
Defrosting
4-way valve 1 restart switching
Oil recovery
Under expansion valve initialization
At protective operation
Central discharge temperature protection
High pressure protection
Compressor stop condition
When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity ", all the compressors
are stopped.
But, in the following case, the compressor operates in accordance with operation of each mode.
Defrosting
Oil recovery
5-1-2 COMPRESSOR OUTPUT PATTERN
The output pattern of a compressor is defined as shown below.
OUTPUT PATTERN
COMPRESSOR 1
(2HP)
COMPRESSOR 2
(4HP)
COMPRESSOR 3
(6HP)
Step 0
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Compressor output pattern
5-1-3 3 MINUTES RESTART PREVENTION (3 MIN ST)
When the compressor is stopped, the compressor does not start on any condition for 3 minutes afterwards.
But, this function is excluded when defrosting, oil recovery is performed and the power is turned on.
– 43 –
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...