ERROR
CONTENTS
ERROR CAUSE
REMEDY
ERROR
CODE
Communication
error
1. When power turned off, then turned on
again:
1) If error not generated again, PC board
is normal. Therefore, remove noise
sources near outdoor unit.
2) If error generated again, perform
following, in addition to removing noise
sources.
1. Affect of extraneous noise.
1. Generation condition.
Communication from indoor
units cuts off certain time.
2. Corresponding operation.
1) When communication error
generated 90 seconds after
outdoor unit circuit board
error 1 generated, all
compressors stopped.
2) When communication from
all indoor units cuts off
certain time, all compressors
stopped and error display
to outdoor unit LED.
3) For other than the above,
only indoor units that
completed communications
are operation target. Error
display to outdoor unit LED.
3. Reset condition.
Communication with indoor
units restored.
1F
2. Check if communication line connected
to all indoor units.
3. Check indoor units power supply.
4. Check insertion of indoor unit
communication PC board and outdoor
unit communication PC board.
5. 1) If communication error generated
after outdoor unit circuit board error
generated, replace PC boards in
following order and check operation.
(1) Outdoor unit communication PC board.
(2) Outdoor unit control PC board.
2) If some indoor units in same refrigerant
operated, replace PC boards in
following order and check operation:
(1) Communication PC board of indoor
unit that generated communication
error.
(2) Control PC board of indoor unit that
generated communication error.
3) When all indoor units in same
refrigerant system generate an error
and compressor does not operate,
replace PC boards in following order
and check operation.
(1) Outdoor unit communication PC board.
(2) Outdoor unit control PC board.
(3) Indoor unit communication PC board.
(4) Indoor unit control PC board.
2. Communication line not
connected, contact faulty, or
line open.
3. Indoor unit power OFF.
4. Indoor unit communication PC
board or outdoor unit
communication PC board
insertion faulty.
5. PC board faulty.
– 102 –
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...