ERROR
CONTENTS
ERROR CAUSE
REMEDY
ERROR
CODE
Discharge
temperature 3
error
1. Check for leak and check additional
refrigerant amount and recharge
suitable refrigerant.
1. Gas leak or refrigerant level
low.
1. Generation condition.
Discharge temperature 3
remains 130 C or greater for
40 minutes and compressor
3 stopped 2 times or more.
2. Corresponding operation.
Error display to outdoor unit
LED and error output to
communication bus line.
3. Reset condition.
When all the following
conditions are satisfied:
1) Discharge temperature
protector 3 reset.
2) Discharge temperature
protector not operated for 40
minutes or longer.
23
2. Check outdoor fan motor operation.
Remove wind path obstruction. If fan
motor faulty, replace motor.
3. Check for loose or dislodged discharge
temperature sensor TH
D3
wiring and
check TH
D3
resistance. If abnormal,
replace sensor.
4. Check operation and coil resistance of
following electronic expansion valve. If
abnormal, replace electronic expansion
valve.
Coil resistance measurement points.
Red-white, red-orange, brown-yellow,
brown-blue.
(1) Outdoor unit electronic expansion
valve EEV1 and EEV2 Coil resistance:
192 +/-19 ohms.
(2) Indoor units electronic expansion valve
EEV Coil resistance: 150 +/-50 ohms.
5. Check operation of following solenoid
valves. If operation faulty, replace
solenoid valve.
Cooling operation.
(1) Outdoor unit solenoid valve SV1.
(2) RB unit solenoid valves SV
S
Heating operation.
(3) Outdoor units solenoid valves SV1,
SV7, and SV8.
(4) RB unit solenoid valve SV
D
.
Heat recovery operation (1), (2), (3), (4).
2. Outdoor fan motor faulty.
3. Discharge temperature
sensor TH
D3
faulty.
4. Electronic expansion valve
operation faulty.
5. Solenoid valve operation
faulty.
– 105 –
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...