ERROR
CONTENTS
ERROR CAUSE
REMEDY
ERROR
CODE
0D
1. Generation condition
Thermistor short or open
detected.
2. Corresponding operation
Indoor unit stopped, error
display to indoor unit LED,
and error output to
communication bus line.
3. Reset condition
Thermistor detection value
other than short or open.
1. Generation condition
Float SW ON continuously
for 3 minutes.
2. Corresponding operation
Indoor unit stopped, error
display to indoor unit LED,
and error output to
communication bus line.
3. Reset condition
Float SW turned OFF.
1. Clean drain hose.
2. Clean drain outlet.
3. Check drain pump operation. If faulty,
replace pump.
4. When float SW shorted, replace SW.
1. Drain hose clogged.
2. Drain outlet clogged.
3. Drain pump faulty.
4. Float SW operation faulty
(short)
Blower tempe-
rature thermistor
error
11
Drain abnormal
1. Generation condition
Room temperature thermistor
detected temperature
exceeds 60 C continuously
for 30 minutes or longer
during indoor unit operation.
2. Corresponding operation
Indoor unit stopped, error
display to indoor unit LED,
and error output to
communication bus line.
3. Reset condition
Reset by turning power off
and on again.
12
Room temperature
thermistor error
1. Generation condition
Fan speed feedback by large
type ceiling model (AB30 or
above) +/-400rpm or greater
relative to target speed.
2. Corresponding operation
Indoor fan stopped, error
display to indoor unit LED,
error output to
communication bus line.
3. Reset condition
Reset by turning power off.
13
Indoor unit fan
error
1. Check for loose or dislodged blower
temperature thermistor connector.
2. Check resistance of blower temperature
thermistor. If abnormal, replace thermistor.
1. Connector connection faulty.
2. Blower temperature thermistor
faulty.
1. Check for loose or dislodged room
temperature connector.
2. Check resistance of room temperature
thermistor. If abnormal, replace
thermistor.
1. Connector connection faulty.
2. Room temperature
thermistor faulty.
1. Check indoor fan motor lead wire
wiring.
2. Check if rated power line voltage
supplied.
1. Indoor fan motor lead wire
connection faulty.
2. Power line voltage abnormal.
1. Generation condition
Communication impossible
between standard wired remote
controller and indoor unit.
2. Corresponding operation
Error display to indoor unit LED.
3. Reset condition
Standard wired remote
controller communication
restored.
18
Communication
error
(indoor unit-
remote controller)
1. Check if communication line connected
to each indoor unit. Check for
communication line open and loose
connection.
2. Replace indoor unit control PC board.
3. Replace standard wired remote
controller PC board.
1. Communication line not
connected, connector faulty,
or line open.
2. Indoor unit control PC board
faulty.
3. Standard wired remote
controller PC board faulty.
– 93 –
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...