3. Abnormal sound is heard from the indoor unit.
PCB LED
1 to 6
LCD
LED display
Remarks
Cause
Remote
controller
Indoor
unit
Outdoor
unit
– 121–
Normal
display
Normal
display
Normal
display
RB unit solenoid valve faulty.
SVb1, 2 solenoid valve faulty.
When heating operation starts,
a voltage (AC220V) is applied to
indoor unit control PCB CN6
(across terminals 3-4), but 3
minutes later a loud refrigerant
rushing sound is generated from
the RB unit.
Coil resistance : 1200~1500
Indoor electronic expansion
valve opening faulty.
Coil resistance (red-white,
red-orange, brown-blue,
brown-yellow) : 100~200
Indoor unit
other than the
relevant indoor
unit does not
perform cooling.
Indoor electronic expansion
valve opening faulty.
Fully open (open excessively)
Cooling operations performed.
The area (heat exchanger) near
the air diffuser is not cooled even
after several minutes have
elapsed since the relevant
indoor unit was stopped.
(Gas pipe is cold.)
When the electronic expansion
valve is open excessively, other
indoor units may not operate at
full capacity or a loud refrigerant
rushing sound may be generated.
Indoor unit
other than the
relevant indoor
unit does not
perform cooling.
Indoor unit heat
exchanger icing.
Indoor unit electronic expansion
valve opening faulty.
Fully open (open excessively)
Cooling stopped
The area (heat exchanger) near
the air diffuser of the stopped
relevant indoor unit is cold.
(Gas pipe is cold.)
When the electronic expansion
valve opens, the indoor heat
exchanger may ice while
stopped and water leakage or
other trouble may occur.
Indoor unit
other than
relevant indoor
unit does not
perform heating.
Indoor unit electronic expansion
valve opening faulty.
Full open (open excessively)
Heating operation
When the relevant indoor unit
performs the heating operation
or another indoor unit performs
the heating operation, the indoor
unit discharge temperature does
not become high and the high
pressure becomes low.
Indoor unit electronic expansion
valve opening faulty.
Full open (open excessively)
Heating stopped.
When the relevant indoor unit or
another indoor unit performs the
heating operation, the indoor unit
discharge temperature does not
become high and the high
pressure become low.
System does
not cool/heat
Outdoor cool/heat switching
4-way valve (4WV1) faulty.
(Cooling/heating pump type only)
28 dia. gas piping temperature
corresponding to 4WV1
energized state(cooling,
de-energized, heating,
energized(AC220V) is abnormal
(cooling : cold, heating : hot).
4-way valve coil resistance
: 1200~1500
Outdoor heat exchanger
switching 4-way valve (4WV2,
4WV3, 4WV4) or solenoid valve
(SV7, SV8) faulty.
Check the heat exchange
operation capacity at the outdoor
control PCB LED.
The energized state (AC220V)
of the heat exchange 4-way valve
and solenoid valve corresponding
to it is abnormal. (Separate
sheet 1)
When a 4-way valve or solenoid
valve is faulty, the high pressure
rises during the cooling operation
and the low pressure drops
during the heating operation.
Coil resistance : 1200~1500
Installed piping is unsuitable.
Liquid piping diameter is
incorrect.
Check the indoor unit capacity
and pipe diameter.
When the diameter is large, a
refrigerant rushing sound will be
generated and when the
diameter is small, capacity will
be insufficient.
Check method
(Error state check method)
Symptom that
can occur other
than title
Body
LED
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...