ERROR
CONTENTS
ERROR CAUSE
REMEDY
ERROR
CODE
High-pressure
error
1. Open ball valve fully.
1. Ball valve not open
completely.
1. Generation condition.
When any of following
conditions satisfied:
1) High-pressure protection
stops compressor 2 times or
more in 40 minutes.
2) High-pressure SW operated
after restarted 3 minutes
after compressor stopped by
high-pressure protection.
2. Corresponding operation.
Error display to outdoor unit
LED and error output to
communication bus line.
3. Reset condition.
When all of following
conditions satisfied:
1) High pressure SW reset after
restarting 3 minutes after
compressor stopped by
high-pressure protection.
2) High pressure protection not
operated for 40 minutes or
longer.
* High pressure SW set value
3MPa OFF , 2.4MPa ON
24
2. Check required installation dimensions.
3. Clean heat exchanger or remove
foreign matter.
4. Check outdoor fan motor operation.
Remove wind path obstruction. If fan
motor faulty, replace motor.
5. Check pressure using pressure gauge.
If pressure SW faulty, replace SW.
2. Outdoor unit short cycle.
3. Outdoor heat exchanger dirty
or clogged with foreign matter.
4. Outdoor fan motor faulty.
5. Pressure SW faulty.
6. Remove obstruction.
7. Clean filter.
8. Check indoor fan motor operation. If
fan motor faulty, replace motor.
9. Check operation and coil resistance of
following electronic expansion valve. If
faulty, replace electronic expansion
valve.
Coil resistance measurement points
Red-white, red-orange, brown-yellow,
brown-blue
(1) Outdoor unit electronic expansion
valve EEV1 and EEV2 Coil resistance:
192 +/-19 ohms.
(2) Indoor units electronic expansion valve
EEV Coil resistance: 150 +/-15 ohms.
10. Check operation of following solenoid
valves.If operation faulty, replace
solenoid valve.
Cooling operation
(1) Outdoor unit solenoid valve SV
S
(2) RB unit solenoid valve SV
S
Heating operation
(3) Outdoor units solenoid valves SV2,
SV7, and SV8
(4) RB unit solenoid valve SV
D
Heat recovery operation (1), (2), (3),
(4)
11. Remove indoor and outdoor
installation conditions and other
overload causes.
6. Indoor unit short cycle.
7. Filter clogged.
8. Indoor fan motor faulty.
9. Electronic expansion valve
operation faulty.
10. Solenoid valve operation
faulty.
11. Overload
– 106 –
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...