2. System does not cool or heat
LED display
Indoor
unit
Outdoor
unit
Remote
controller
PCB LED
1 to 6
Error
display
(Communi-
No display
Power not supplied to
outdoor unit.
Circuit breaker OFF.
Power line faulty.
Voltage across R-S, S-T,
and T-R: 380~415V
Voltage across R-N,S-N,
Normal
display
Outdoor unit system type
selector switch (DIP SW7-1,7-2)
setting error.
Cold air is blown from the indoor
unit during the cooling operation,
but warm air is not blown from
Set to heat recovery type/
cooling only type with cooling/
heating pomp type piping.
Indoor unit refrigerant
system address setting
(SW 7,8) error.
When the indoor units are
operated one by one,there is an
indoor unit whose outdoor unit
Set the address to the same
refrigerant system address of the
outdoor unit to which the
refrigerant piping is connected.
Indoor unit indoor unit address
(SW 5) setting error.
(address duplicated)
Installed piping is unsuitable.
piping is too long.
Refrigerant leakage.
Check for leaks using a gas
detector.(Refrigerant charged
state)
Regarding air tightness test after
installation or repair,pressurize
the system with nitrogen(3.5MPa)
and test for leaks with soapy
water and allow the system to
stand for 24 hours,and then
check that there is no drop in
pressure.(Note: When the
Insufficient gas (light)
During the cooling operation,the
discharge temperature does not
become low when all the indoor
units are operated.
During the heating operation,
the discharge temperature does
not become high when only one
indoor unit is operated.
For light gas insufficiency,
capacity drops only in a specific
operation state.(Note that this
symptom resembles faulty indoor
unit electronic expansion valve
opening.)
– 116 –
Normal
display
Normal
display
Normal after the power reset.
LCD
Body
LED
Symptom that
can occur other
than title
Check method
(Error state check method)
Remarks
cation error)
Error
display
(Communi-
cation error)
Cause
Check each outdoor unit power
supply terminal board(Power)
voltage.
and T-N: 220~ 240V.
Outdoor unit is leaking(shorted).
(Circuit to which a voltage is
applied when energized is
leaking electricity.)
Trip the outdoor unit circuit
breaker immediately after setting
the circuit breaker to ON.
The resistance across each
outdoor unit power supply
terminal board(Power)
terminal and outdoor unit
metal part approaches zero.
When shorted,there is a
combination that shows an
outdoor unit power supply
wires(R-S,S-T,T-R,R-N,S-N,T-N)
correlative resistance of nearly
zero.
Outdoor unit is leaking(shorted).
(Circuit to which a voltage is
applied only when operating is
leaking electricity.)
Trip the outdoor unit circuit
breaker during operation.
The resistance value of the
outdoor unit electric parts and
outdoor unit metal part
approaches zero.
When shorted,there is a
combination,which indicates an
electric parts correlative
resistance near zero.
(Real length 100m or more)
Installed piping is unsuitable.
Gas piping diameter is
incorrect.
the indoor unit during the heating
operation.
does not operate.
Operate each indoor unit for 5
minutes or more.
The relevant outdoor unit stops
and starts midway.
(Compressor capacity and heat
exchange capacity at outdoor
unit LED is not correct.)
Multiple indoor units in one
refrigerant system must not be
set to the same indoor unit
address.
Check the outdoor unit and
indoor unit installation site and
estimate the piping length.
When the piping is too long,
the cooling capacity may be
insufficient.
Heating capacity may also be
insufficient,but cooling capacity
is made insufficient.
Check the indoor unit capacity
and piping diameter.
When the gas piping diameter is
large,cooling capacity will be
insufficient.
Heating capacity may also be
insufficient at heating,but cooling
capacity is made insufficient.
outdoor temperature
C,the pressure
changes 5
changes 0.06MPa.)
Summary of Contents for AirStage AB12
Page 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Page 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Page 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Page 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Page 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Page 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Page 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Page 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Page 135: ...Models AOY90TPAMF 135 ...
Page 137: ...Models AOY90TPAMF 137 ...
Page 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Page 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Page 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Page 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Page 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Page 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Page 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Page 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Page 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Page 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Page 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Page 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Page 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...