27
Setting of input type
[Description]
• Input type can be set.
• The main unit is determined accord-
ing to input type (2 types shown
below). Set a code that conforms
with the main unit.
• Input type can be changed within the
same types. It cannot be changed
to different types.
Type I : Thermocouple (9 types),
Resistance bulb (1 type)
Type II : Voltage, current
Example) Altering thermocouple from K to T on Type I
Key operation
Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
P-n2 is displayed.
Press the or key to display
7.
“3” is displayed, and it is clear
thermocouple K is selected.
Press the SEL key for 3 seconds
when you need to display the opera-
tion status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
ENT
SEL
DATA
• On the Type II, when selecting volt-
age input or current input, it becomes
necessary to change the code and
connect an resistor 250
Ω
to the in-
put terminal when current input is
used.
• When changing the voltage input,
remove the resistor 250
Ω
from the
input terminal.
• Input type and code
①
Input type code table
Change of software
After changing software, turn OFF
the power and then turn ON once
again.
Type
Resistance bulb
Thermocouple
• Pt100
• J
• K
• R
• B
• S
• T
• E
• N
• PL-II
1
2
3
4
5
6
7
8
12
13
1 to 5V DC, 4 to 20mA DC
16
Code
(P-n2)
Related parameter: P-SL (Page 29)
P-SU (Page 29)
P-dP (Page 33)