21
Output convergence value (Setting range: -100.0 to 100.0%)
Anti-reset wind up
[Description]
• This setting is not require unless it
is necessary.
This function is used to suppress
over-shoot.
• Anti-reset wind up (Ar) is automati-
cally set in optimum value by P.I.D
auto-tuning.
The value of over-shoot can be con-
trolled by setting BAL.
• By setting anti-reset wind up (Ar)
in optimum value, unwanted integral
action can be cut and over-shoot is
reduces.
(Note) This controller has fuzzy con-
trol function, so over-shoot
can be minimized without us-
ing BAL and Ar. This param-
eter is used only for inter-
changeability with former
type (PYZ series).
Example) Altering anti-reset wind up of 80
°
C to 60
°
C
Key operation
Description
Press the SEL key to display P.
Press the SEL key repeatedly until
is displayed.
Press the or key to display
60.
Press the DATA key once.
Current data (80
°
C) of anti-reset
wind up is displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, anti-
reset wind up data is registred.
Display
SEL
ENT
SV
DATA
SEL
(Setting range: 0 to 100%FS)
(No display prior to delivery)
PV
AR value
Integral action is cut in this range.
Integral action is performed in this range.
Integral action is cut in this range.
Time
AR value
SV