2
2
Operation
The setting of set values (SV) and internal parameters of the Micro Controller X are explained in
the following.
2-1
Parameter Table
On Micro Controller X, parameters are classified into No. 1 and No. 2 blocks according to operation frequency. No. 1 and No.
2 blocks are used for initial setting and whenever necessary.
①
No. 1 block parameter table
Parameter display
symbol
Initial set value
prior to delivery
User’s
set value
Parameter
mask DSP
Name
Description
Page
〜
〜
〜
〜
ProG
Lamp soak start/stop
P
Proportional band
I
Integral time
D
Derivative time
Setting range; 0.0 to 999.9% (for input range)
Setting range; 0 to 3200 sec.
Control stability is enhanced with input change.
It reacts quickly with change of small deviation at large
derivative time (D). (Setting range: 0.0 to 999.9 sec.)
L
H
TC
HYS
HB
AT
TC2
CooL
db
PLC1
PHC1
PCuT
BAL
AR
LoC
STAT
SV-1
SV-4
〜
TM1r
TM4r
〜
TM1S
TM4S
Mod
1-1
1-2
1-4
1-8
1-16
1-32
1-64
1-128
2-1
2-2
2-4
2-8
2-16
2-32
2-64
2-128
3-1
3-2
3-4
3-8
3-16
3-128
4-4
4-32
3-32
4-1
4-8
4-64
3-64
4-2
4-16
4-128
5-1
24
6
7
8
9
10
11
12
13
15
16
17
18
19
19
20
21
21
22
23
23
23
23
23
oFF
5.0
240
60.0
10
10
Contact output: 30
SSR/SSC drive output 2
Contact output: 30
SSR/SSC drive output 2
1
0.0
0
1.0
0.0
-3.0
103.0
—
Single: 0.0
Dual : 50.0
100%FS
0
OFF
0%FS
0.0
0.0
0
Lower limit
alarm
Upper limit
alarm
Used to set lower limit operation of alarm. Setting within
input range is possible (option).
Used to set upper limit operation of alarm. Setting within
input range is possible (option).
Control output 1
proportional cycle
2-position action
hysteresis width
Heater burnout
alarm
Used to set control output proportional cycles.
(Setting range: 1 to 150 sec.)
Used to set hysteresis width at 2-position action.
(Setting range: 0.0 to 50.0%FS)
Used to set value of heater burnout detection (option).
(Setting range: 1.0 to 50.0A) [Alarm function OFF at 0]
Auto-tuning
Control output 2
proportiona cycle
Used to set PID parameters by auto-tuning.
0: None (auto-tuning released or not executed)
1: Execution (standard type; auto-tuning is executed by SV value)
2: Execution (low PV type; auto-tuning is executed at -10FS
of SV value)
Used to set proportional cycle of cooling side control output
(option). (Setting range: 1 to 150 sec.)
Cooling side
proporitonal
band coefficient
Used to set cooling side proportional band coefficient (option).
(Setting range: 0.0 to 100.0)
The setting of 0 will lead to ON-OFF operation.
Cooling side pro-
portional band shift
Used to shift cooling side output value (option).
(Setting range: -50.0 to +50.0)
Output 1 lower
limit setting
Output 1 higher
limit setting
Peculiar parameter for device. Do not use.
Output conver-
gence value
Antireset
wind up
Setting range: -3.0 to 103.0%
Setting range: -3.0 to 103.0%
Function to suppress overshoot.
Used to suppress overshoot due to integral action.
(Setting range: 0 to 100%FS)
Designates enable or disable to change the parameter setting.
0: Change of all parameter setting is possible.
1: Change of all parameter setting is not possible.
2: Change of set value (SV) only is possible.
Key lock
Ramp/soak present
position display
Used to display present ramp/soak position (option).
No.1 to No.4
target value
Used to set ramp/soak target value (option).
(setting range: 0 to 100%FS)
Used to set time for segment of ramp (option).
(setting range: 0 to 99h59m)
Used to set time for segment of soak (option).
(setting range: 0 to 99h59m)
Setting of ouptut at power ON start and end, at power OFF,
and setting of repeat action (option).
No.1 to No.4
ramp segment
time
No.1 to No.4
soak segment
time
Ramp/soak func-
tion mode setting
Lamp soak control
oFF: Stop
rUn: Start
HLd: Pause