— 15 —
Table 4
Table 1
0 to 19
P-n1
P-n2
P-dp
Specifying control operation
0.0 to 900.0 sec.
P-dF
Input filter (Time constant)
*2
0.0 to 50.0%FS (engineering unit )
P-An
Alarm insensitive zone
OFF: PID control
ON : FUZZY control
FUZY
Specifying control method
Note 6
0 to 255
dSP1
dSP7
to
to
Specifying parameter mask
Parameter
display code
Description
Setting range (Setting unit) Reference
0 to 16
Input type setting
Table 2
P-SL
Setting of lower limit in the range
-1999 to 9999 (engineering unit)
Note 3, Note 4
Table 2
P-SU
-1999 to 9999 (engineering unit)
Note 3, Note 4
Setting of upper limit in the range
Setting of decimal
point position
0 to 2 Note 2, Note 3
1
2
0: No decimal point
Table 3, *2
P-AH
0 to 11
Alarm type, Alarm type 1
Table 3, *2
P-AH
0 to 15
Alarm type, Alarm type 2
PVOF
PV offset
-10 to 10%FS (engineering unit)
Note 1) Always set to 0 before using.
Note 2) 2 is valid only if voltage and current are applied.
Note 3) When P-SL/P-SU/P-dP is changed, check that all the parameters including the SV
are properly assigned.
(They may have change)
Note 4) Not indicated if no HB occurs.
Note 5) The setting of 0 is for current output.
Don’t set 0 at contact or SSR driving output.
It is recommended more than 30 at contact or more than 1 at SSR driving output.
Note 6) If you miss setting to dSP1 to dSP7, any parameters that you want to see
don't apper.
Before you change them, record the current value of them.
Take care enough to change them.
*1: Not indicated without ramp/soak.
*2: Not indicated without alarm.
*3: Not indicated for current output.
*4: Not indicated at shipment from factory.
*5: Not indicated without control output 2.
*6: Indicated only when control output 2 is relay or SSR drive output.