32
Example) Altering cold junction compensation from ON
to OFF
Key operation
Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
RCJ is displayed.
Press the or key to display
OFF.
Current data is displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
SV
DATA
ENT
Setting of RCJ compensation
[Description]
• This function is used whether or not
RCJ compensation (cold contact
compensation) is used for thermo-
couple input. Normally, it should
be used at ON (RCJ compensation)
which has been set prior to delivery
from the factory.
• It should be set to OFF only when
cold contact compensation is not
required, for example, when cold
contact compensation is to be made
with external circuit or temperature
deviation needs to be obtained.