24
Example) Start ramp/soak operation (rUn) from local
operation (oFF)
Key operation
Description
Press the SEL key to display ProG.
Press the or key to display
.
Press the DATA key. Current data
( ) is displayed.
Press the SEL key when you need to
display the operation status display.
After pressing the ENT key, setting
data of ramp/soak control is register-
ed.
Start operation according to preset
ramp/soak patterns.
Display
SEL
ENT
SEL
DATA
Setting of ramp/soak control (ProG) (option)
[Description]
• This function is used to change time
and set value (SV) automatically
according to preset pattern. Up to 4
ramp/soak programs can be used.
• The No. 1 ramp starts from measure-
ment value (PV) just before the ex-
ecution of program.
• It is also possible to run the program
automatically at power ON (power
ON start function).
Ramp .... Range of change in set value
toward target value
Soak ..... Range of unchanged set
value, the same as target
value
SV3
SV2
SV1
SV4
PV
TM1R TM1S
TM2S
TM2R
TM3R
TM4R
TM3S
TM4S
Set
value
No.1
ramp
No.1
soak
No.2
soak
No.3
soak
Time
No.4
soak
No.2 ramp
No.3 ramp
No.4 ramp
Related parameter: STAT (Page 23)
SV-1
〜
SV-4 (Page 23)
TM1r
〜
TM4r (Page 23)
TM1s
〜
TM4s (Page 23)