3
No. 2 block parameters are used for setting the initial set values, and for special operation and setting.
②
No. 2 block parameter table
Parameter display
symbol
Initial set value
prior to delivery
User’s
set value
Parameter
mask DSP
Name
P-n1
P-n2
P-dF
P-SL
P-SU
P-AL
P-AH
P-An
RCJ
P-dP
PVOF
SVOF
P-F
PLC2
PHC2
FUZY
ADJO
ADJS
OUT
dSP1
dSP7
Setting of
control method
Setting of input
type
Input filter
parameter
Setting of lower
limit range
Setting of higher
limit range
Setting of lower limit
alarm (ALM2) type
Setting of higher limit
alarm (ALM1) type
Setting of alarm action type
Setting of alarm
hysteresis
Setting of alarm output ON-OFF hysteresis width
(Setting range: 0 to 50%FS)
RCJ compensa-
tion setting
on: RCJ compensation ON (cold contact compensation is performed)
off: RCJ compensation OFF (cold contact compensation is not performed)
Setting of
decimal point
position
PV offset
SV offset
Selection of unit
°
C/
°
F
of measured value input
Output 2 lower
limit setting
Output 2 higher
limit setting
FUZY control
setting
ON: FUZY control is performed.
OFF: Normal PID control is performed.
User adjust zero
adjustment
User adjust span
adjustment
Used for shifting input zero side by user adjust function.
Output value
(MV) display
Parameter skip
Items shown in are not displayed. If necessary, they are able to be displayed and set by using the dsp1 to dsp7 function of No.2 block parameter.
Setting of parameter display “yes or no”
Setting of normal/reverse action of set output and burnout
direction.
Setting of input type
Setting of input filter parameter (second)
(Setting range: 0.0 to 900.0 sec.)
Setting of lower limit input range
Setting of higher limit input range
Setting of alarm action type
Selects decimal point position of PV/SV display.
No decimal point : “0”
“1”
“2”
Shift of input value (PV) display.
(Setting range: -10 to 10%FS)
Shift of set value (SV) display. SV display remains unchanged.
(Setting range: -50 to 50%FS)
Measured value is selected, so other parameters need to be
changed.
°
C display: C
°
F display: F
Setting range: -3.0 to 103.0%
Setting range: -3.0 to 103.0%
Used for shifting input span side by user adjust function.
display of present output value (MV)
As per ordering
specification
As per ordering
specification
As per ordering
specification
As per ordering
specification
9
5
5.0
1
on
As per ordering
specification
As per ordering
specification
0
0
-3.0
103.0
OFF
0
0
—
Setting is made
according to
code symbol
5-8
5-16
5-32
5-64
5-128
6-1
6-2
6-8
6-4
6-16
6-32
6-64
6-128
7-1
7-2
7-8
7-16
7-32
—
39
25
5-4
27
26
29
29
30
30
28
32
33
34
35
36
19
19
37
38
38
—
Description
Page
〜
〜