![Fuji Electric MICREX-SX series User Manual Download Page 39](http://html.mh-extra.com/html/fuji-electric/micrex-sx-series/micrex-sx-series_user-manual_2341770039.webp)
4-3
Section 4 High-speed Counter
4-1 High-speed Counter Specifications
(3) High-speed counter match interrupt %MW10.275
(4) High-speed counter current value, set value, preset current value %MD10.276 to 284
Address
Name
Description
%MX10.275.0
Match interrupt
This is a flag for setting conditions for an event task.
It is used for the match interrupt for high-speed counter. If the current value coincides
with the set value when match interrupt is enabled, the set event task is started.
%MX10.275.1
|
%MX10.275.15
Not used
Address
Name
Description
%MD10.276
High-speed counter
current value
Stores the current value of high-speed counter.
%MD10.278
Not used
%MD10.280
High-speed counter
comparison value setting
Stores the set value to compare with the current value.
The value set in this area takes effect when the comparison value set flag
(%MX10.272.6) is set ON.
%MD10.282
Not used
%MD10.284
High-speed counter
preset value setting
Stores the preset current value of high-speed counter.
The value set in this area takes effect when the current value preset flag
(%MX10.272.7) is set ON.