4-1
Section 4 High-speed Counter
4-1 High-speed Counter Specifications
<Special notes>
Wiring must use the shield line. Ground shielded wires.
Please connect the shield appropriately according to the specification of the pulse encoder and the connection with the
controller.
The signal from the encoder might malfunction by interfering with A phase and B phase when the wiring between the
encoder and the inverter is long. In this case, please execute measures such as; wiring shorter cable, cable of smaller
electrostatic capacity, etc.
Item
Specification
No. of input channels
1 channel
Phase
2-Phase signal (90 phase difference)
Multiplication
Multiplication 2 or 4
Max. input frequency
50 kHz
Counting range
Signed 32-bit binary addition and subtraction counter
(DINT type: -2147483648 to 2147483647)
Current value reset function
Reset by application (using system memory for high-speed counter)
Current value preset
Preset by application (using system memory for high-speed counter)
Interrupt function
It is possible to activate one event task when "the counter current value and
comparison register value have become equal".
Input signal indication
None
4-1-1 List of specifications