1-9
Section 1 PLC Specifications
(5) Memory error factor %MW10.8, %MW10.9 (Read only)
System operation after a memory error has occurred
Any memory backup error resets the entire user memory area to 0 (zero). Note that in most cases, since %MX10.8.0 to
%MX10.8.3 are set to “ON” when a hardware fault has occurred, cycling the power source may cause a memory error to be
repeated.
(6) Application error factor %MW10.12, %MW10.13 (Read only)
1-2 PLC Internal Memory
Address
Name
Description
Level
%MX10.8.0
System ROM error
Set to "ON" when an error has occurred in the system ROM in
this board.
Fatal fault
%MX10.8.1
System RAM error
Set to "ON" when an error has occurred in the system RAM in
this board.
Fatal fault
%MX10.8.2
Application ROM error
Set to "ON" when an error has occurred in the user program
ROM in this board.
Note: Set to "ON" when an error has occurred in the user ROM
card.
Fatal fault
%MX10.8.3
Application RAM error
Set to "ON" when an error has occurred in the user program
RAM in this board.
Fatal fault
%MX10.8.4
|
%MX10.8.14
Not used
%MX10.8.15
Memory backup error
Set to "ON" when no power-failure-time data is retained. May
clear the error condition by using an application program.
Nonfatal fault
Address
Name
Description
Level
%MW10.12.0
System definition error
Set to "ON" when an error has been found in the system
definition.
Fatal fault
%MW10.12.1
Application program error
Set to "ON" when an error has been found in the Application
program.
Fatal fault
%MW10.12.2
|
%MW10.12.15
Not used
%MW10.13.0
Not used
%MW10.13.1
Application program error
Set to "ON" when an error has been found in the Application
program.
Nonfatal fault
%MW10.13.2
|
%MW10.13.3
Not used