7.10 Selection of sensor mounting method
Mounting methods available for the sensor are
V method and Z method as illustrated.
To select the mounting method;
Press the key, the “SENSOR MOUNT” is
reversed from white to blue.
Press the
ENT
key. The “SENSOR MOUNT”
screen will appear.
Select either V or Z method by the or
key.
Remarks
Select the V method generally. Use the Z method in
the following cases:
• Ample space is not provided.
• High turbidity
• Weak receiving waveform
• Thick scale is deposited on the pipe internal surface.
V method
Z method
(Except.
Small sensor FSSD1)
ENT