![Fuji Electric FSC-2 Instruction Manual Download Page 124](http://html1.mh-extra.com/html/fuji-electric/fsc-2/fsc-2_instruction-manual_2341885124.webp)
INF-TN2FSC-E
115
(6) Move the digit by the or key and enter numeric
values by pressing the or key.
After entry, press the
ENT
key to set the range. The
full scale value will be set.
(7) Make settings for output limit high/low (upper/lower
limit for analog output).
Setting limit: Output limit low –20 to 0%
Output limit high 100 to 120%
Select “OUTPUT LIMIT LOW” by the or key.
Press the
ENT
key, and you are ready to set the output
limit low.
(8) Move the digit by the or key and enter numeric values by pressing the or key.
After entry, press the
ENT
key to set the range.
(9) Select “OUTPUT LIMIT LOW” by pressing the or key.
Set the output limit high in the same manner as the output limit low.
(3) Set the range type (single range or bi-directional
range).
Select “RANgE TYPE” by pressing the or
key.
(4) Press the
ENT
key to display the RANgE TYPE
screen.
Select the range type by the or key and press
the
ENT
key.
(5) Set the full scale value for output range.
Setting range:
When the range kind is velocity or flow rate
0.000, ±0.300 to ±32.000m/s
(Flow velocity conversion)
When the range kind is thermal flow rate
0.000 to 9999999999
Select “FULL SCALE” by pressing the or key.
Press the
ENT
key, and you are ready to set the full scale.
Set RANgE so that flow rate to be measured exceeds 1.2 times its maximum value.
If measured value exceeds the set value, the status display on the measurement screen turns
“E4: RANgE OVER”.
Unless analog output is used, set the full scale setting at 0, and “E4: RANgE OVER” is not
displayed.
CAUTION