INF-TN2FSC-E
105
Current Input Caribration procedure
ENT
Input 4mA from external.
Under calibration of 4mA
ENT
ENT
Input 20mA from external.
Under calibration of 20mA
End of calibration
After calibration, the “End of
Calibration” message appears
under the calibration button.
• Analog input has already been calibrated on the factory setting
• When you interrupt the calibration in the middle, the calibration value will be
lost.
If you interrupt the calibration, start from the beginning again.
• Calibrated analog inout required for AI measurement.
CAUTION