SUPER RUNNER SERIES GAS FRYERS
CHAPTER 1: INSTALLATION INSTRUCTIONS
1-2
For units equipped with legs: Lift the unit and move it into its final position. Do not drag or push the fryer into position.
Doing so may damage the legs. Level the unit front to back and side to side. If the fryer is not level, the unit will not
function efficiently. Super Runner Series gas fryers cannot be curb mounted and must be equipped with either legs or
casters provided.
A.
Adjust leg height with an adjustable or 1-1/16-inch (27-mm) open-end wrench by turning the hexagon-shaped foot
on the bottom of the leg.
NOTE:
The foot is for minor leg height adjustment only.
Do not adjust outward more
than ¾-inch (19-mm)
.
B.
When leveling the unit, the leg body should be held firmly to keep the leg from bending or rotating while turning the
foot to the required height.
For units equipped with casters: Roll the unit into its final position and lock the front casters.
1.3 Pre-Connection Preparation
WARNING
If the incoming gas pressure is in excess of ½" PSI (3.45 kPa/35 mbar), a step-down regulator will be
required.
NATIONAL CODE REQUIREMENTS:
This equipment is to be installed in compliance with the Basic Plumbing Code of the Building Officials and Code
Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the U.S. Food and Drug
Administration.
This equipment is manufactured to use the type of gas specified on the rating plate attached to the door. Connect
equipment stamped "NAT" only to natural gas and that stamped "PRO" only to LP (Propane) gas.
AUSTRALIAN REQUIREMENTS:
To be installed on a firm, level surface in accordance with AS 5601 / AG 601, local authority, gas, electricity, and any
other relevant statutory regulations. The Australian orifice size and manifold pressures are listed below for the SR42 and
SR62 fryers.
Model
Gas Type
Orifice Size
Manifold Pressure KPa
Manifold Pressure Inches WC
SR62GN Nat
2.53 mm
0.9 KPa
3.6”
SR62GP Prop
1.6 mm
2.4 KPa
9.6”
SR42GN Nat
2.8 mm
0.87 KPa
3.5”
SR42GP Prop
1.65 mm
2.5 KPa
10”
Nominal Heat Inputs (Qn), Gas Type, Orifice Size, Pressures and Adjustments, Orifice Quantity, and Pilot Markings are
listed in the table below:
MODEL*
NOMINAL
HEAT INPUT-
Qn
(BTU)
GAS TYPE ORIFICE
SIZE (MM)
MANIFOLD GAS
PRESSURE
(INCH W.C.)
ORIFICE
QUANTITY
PILOT
MARKING
SR62 GM
150
NAT
LP
2.53(#39)
1.51(#53)
4
11
5
5
26N
16LP
SR52 GM
120
NAT
LP
2.53(#39)
1.51(#53)
4
11
4
4
26N
16LP
SR42 GM
105
NAT
LP
2.80(#35)
1.70(#51)
3.5
10
3
3
26N
16LP
*SR prefix- Super Runner Series
*GM suffix- gas millivolt system with no electrical supply connections required
NOTE: Outlet gas pressure must be adjusted strictly within the above requirements 5 to 10 minutes after the appliance is
operating.
ENGL
ISH
Summary of Contents for Dean Super Runner Series
Page 3: ...Register Your Warranty Online at http fm hal frymaster com qsys lib cgi lib swr290 pgm ENGLISH...
Page 11: ...SUPER RUNNER SERIES GAS FRYERS CHAPTER 2 OPERATION 2 3 2 5 Wiring Diagram ENGLISH...
Page 12: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 15: ...Registre su garant a en l nea en http fm hal frymaster com qsys lib cgi lib swr290 pgm ESPA OL...
Page 23: ...FREIDORAS DE GAS SERIE SUPER RUNNER CAP TULO 2 OPERACI N 2 3 2 5 Diagrama de cableado ESPA OL...
Page 24: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 35: ...FRITEUSES GAZ SUPER RUNNER CHAPITRE 2 MODE D EMPLOI 2 3 2 5 Diagramme de c blage FRAN AIS...