Generator-powered operation
Generator-pow-
ered operation
The power source is generator-compatible.
The maximum apparent power S
1max
of the power source must be known in order to select
the correct generator output.
The maximum apparent power S
1max
of the power source is calculated as follows:
The generator apparent power S
GEN
needed is calculated using the following rule of
thumb:
A smaller generator may be used when not welding at full power.
IMPORTANT!
The generator apparent power S
GEN
must always be higher than the maxi-
mum apparent power S
1max
of the power source.
When using single-phase devices with a 3-phase generator, note that the specified gener-
ator apparent power is often only available as a whole across all three phases of the gen-
erator. If necessary, obtain further information on the single-phase power of the generator
from the generator manufacturer.
3-phase devices:
S
1max
= I
1max
x U
1
x √3
Single-phase devices:
S
1max
= I
1max
x U
1
See device rating plate or technical data for I
1max
and U
1
values
S
GEN
= S
1max
x 1.35
NOTE!
The voltage delivered by the generator must never exceed the upper or
lower limits of the mains voltage tolerance range. Details of the mains voltage tol-
erance can be found in the "Technical data" section.
Summary of Contents for TransSteel 3500 Rob
Page 2: ...2...
Page 4: ...4...
Page 8: ...8...
Page 20: ...20...
Page 21: ...General information...
Page 22: ......
Page 27: ...Control elements and connections...
Page 28: ......
Page 35: ...Installation and commissioning...
Page 36: ......
Page 46: ...46...
Page 47: ...Welding...
Page 48: ......
Page 61: ...61 EN Number 3 Number 4 Number 5...
Page 62: ...62...
Page 63: ...Setup settings...
Page 64: ......
Page 76: ...76...
Page 77: ...Troubleshooting and maintenance...
Page 78: ......
Page 99: ...Appendix...
Page 100: ...100 Spare parts list TSt 3500 Rob TSt 5000 Rob...
Page 102: ...102...
Page 103: ...103...