7.2 Technical specifications - S3 Turbo with partial load values
Description
S3 Turbo 28
Testing institute
TÜV Austria
1)
Test report no.
08-UW/Wels-EX-299/5
Date of issue
04/12/2010
Boiler class as per EN 303-5:2012
4
Nominal output / range
kW
31 / 15.5 - 31
Boiler efficiency (nominal load / partial
load)
%
91.3 / 92.4
1.TÜV Austria Services GmbH, Geschäftsbereich Umweltschutz, Am Thalbach 15, A-4600 Thalheim/Wels
Test data - Emissions in [mg/MJ]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/MJ
80 / 486
Nitrogen oxide (NOx)
mg/MJ
91 / 70
Organic hydrocarbons (OGC)
mg/MJ
3 / 20
Dust
mg/MJ
21 / 8
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/m³
118 / 714
Nitrogen oxide (NOx)
mg/m³
134 / 102
Organic hydrocarbons (OGC)
mg/m³
4 / 30
Dust
mg/m³
30 / 12
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Test report data -
Lambda Control
7
Appendix
Technical specifications - S3 Turbo with partial load values
70
Froeling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.at