Service
E-filter function active
Used to activate/deactivate the electrostatic filter function.
When the filter is deactivated, the bypass flap is open and
the flue gas is fed directly into the chimney.
Time until bypass flap is open
Specifies the time for opening the bypass flap in seconds.
The specified time must correspond at least to the
actuating time of the flap drive.
Close bypass flap when filter switched off
This parameter is set to “NO” by default and should only
be changed after consultation with the manufacturer.
Cleaning interval
Specifies after how many operation hours of the E-filter a
cleaning cycle should be started. Depending on the raw
dust content, this value is set between 4 and 8 hours.
Duration of cleaning cycle
Defines the total time for a cleaning process. Via this
duration, the spray valve is periodically switched on and
off.
On-time of spray valve. Overall cycle 10 sec
Defines the cycle of the spray valve, which is repeated
until the total time (parameter “Duration of cleaning cycle”)
has elapsed. The cycle of the spray valve is set in
percentages of 10 seconds.
Example: On-time of spray valve: 60%, duration of
cleaning cycle: 23s;
Spray value is switched on for 6 seconds, waits for 4
seconds. This cycle is repeated until the total time is
reached. (6s ON - 4s OFF - 6s ON - 4s OFF - 3s ON)
Dry time
Defines the waiting time after a cleaning cycle before the
HV electrodes are activated again.
Is there a siphon fitted?
By default this parameter is set to “YES” and cleaning of
the filter is performed according to the specified interval. In
case of problems with the drain system (e.g. blocked duct)
this parameter can be set to “NO” in the interim. The
cleaning times are then adjusted so that the collection tank
is not overfilled.
Quick/compulsory cleaning active?
Specifies whether the function of the quick/compulsory
cleaning should be active.
Quick/compulsory cleaning: If the output of the HV module
is below 25% for a defined period, a quick cleaning is
carried out during operation. If the output of the HV module
remains below 25%, then a set waiting time is observed
until the next quick cleaning.
Duration of quick cleaning
Defines the on-time of the spray valve during a quick
cleaning.
Minimum time between quick/compulsory cleaning
Specifies the waiting time between two quick cleanings in
minutes.
Cleaning possible from
In conjunction with the parameter “Cleaning possible till”,
this defines a time window in which the automatic filter
cleaning may be activated.
Cleaning possible till
In conjunction with the parameter “Cleaning possible
from”, this defines a time window in which the automatic
filter cleaning may be activated.
IO allocation
Setting of the relevant address for the respective
component for the inputs and outputs on the digital
module.
▪ Address HV in 1
▪ Address HV in 2
▪ Address water sensor 1
▪ Address water sensor 2
▪ Safety switch address
▪ Address HV out 1
▪ Address HV out 2
▪ Address bypass flap open
▪ Address washer valve 1
▪ Address washer valve 2
4
Parameters overview