4.9 Network pump
4.9.1 Network pump - Status
System menu
Network pump
Network return temperature
Display of the current return temperature of the remote
line.
Network pump speed
Specifies the current speed of the network pump.
Return temperature distributor 1
Prerequisite: Variant 1 and feeder pump for distributor 1
installed
Display of the current return temperature from distributor 1.
Speed, distributor 1 pump
Prerequisite: Variant 1 and pump for distributor 1 installed
Display of the current speed of distributor 1 pump.
Return temperature distributor 2 … 4
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Display of the current return temperature from distributor
2 ...4.
Speed, distributor 2 ...4 pump
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Display of the current speed of the distributor 2 … 4 pump.
4.9.2 Network pump - Temperatures
System menu
Network pump
Network return setpoint
Prerequisite: Network pump installed
The network return setpoint is regulated to the value set
here. When the network return temperature reaches the
specified value, the network pumps starts up at minimum
speed.
Return temperature setpoint distributor 1
Prerequisite: Variant 1 and pump for distributor 1 installed
The return temperature from distributor 1 is regulated to
the value set here. When the return temperature from
distributor 1 reaches the specified value, the pump for
distributor 1 starts up at minimum speed.
Return temperature setpoint distributor 2 ... 4
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
The return temperature from distributor 2 ... 4 is regulated
to the value set here. When the return temperature from
distributor 2 reaches the specified value, the pump for
distributor 2 ... 4 starts up at minimum speed.