Minimum value for the reload quantity
If the calculated reload quantity is less than the minimum
value setting, an instruction is displayed to the user that he
need not heat up/reload.
If the boiler is active then charge all storage tanks
Prerequisite: Variant 3 or variant 4
▪ YES: Starting the boiler due to a heating requirement by
the storage tank in the boiler system not only loads this
storage tank, but all of the storage tanks in sub-stations.
This increases the runtime related to a boiler system
start.
Pump outlet for storage tank relief valve
The switch valve switches off part of the layered tank until
an adjustable temperature has been reached in the top of
the layered tank so that the boiler reaches the temperature
more quickly. Once this temperature has been reached,
the switch valve switches back and the entire volume of
the layered tank is available to the boiler.
Invert pump outlet for buffer relief valve
▪ YES: If the valve switches incorrectly, the way it is
controlled can be changed using this parameter.
Parameters overview
4
Buffer tank
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en