E-filter external
Setting
Flue gas
E-filter external
State
Filter status
Displays the current operating status of the E-filter as a
numeric code. The following statuses are possible:
▪ Status “0”: Filter deactivated
▪ Status “1”: Filter off
▪ Status “2”: Filter on
▪ Status “3”: Measuring mode
▪ Status “4”: RFI
▪ Status “5”: Wait for bypass flap
▪ Status “6”: Cleaning - Pause
▪ Status “7”: Cleaning - Rinse
▪ Status “8”: Wait for water sensor
▪ Status “9”: Waiting for drying time
▪ Status “10”: Filter error
▪ Status “11”: Quick cleaning
▪ Status “12”: Waiting for drying time
▪ Status “13”: Cleaning – Waiting
▪ Status “14”: Cleaning – Shaking
▪ Status “15”: Cleaning – Waiting
Filter return signal
Shows the filter status as a numeric code. Following status
values are possible:
▪ Status "0": No error
▪ Status "1": Power supply fault
▪ Status "2": RS485 error
▪ Status "3": Temperature box error
▪ Status "4": High voltage error
▪ Status "5": Wait for ready-to-measure state
▪ Status "6": Values critical
▪ Status "7": Measure
▪ Status "8": Measuring mode error
Water detected
Shows the status of the water sensor in the ash drawer. If
the water sensor detects a water level that is too high, the
E-filter is deactivated.
Time until next cleaning
Shows the remaining time (in minutes) until the next
cleaning process.
E-filter service hours
Shows the operation hours since the E-filter was first
activated.
Number of cleaning processes
Shows the total number of cleaning processes since the E-
filter was first activated.
Output HV module 1 … 4
Displays the current output of the respective HV module as
a numeric code. The following displays are possible:
▪ Output “0”: The current output of the HV module is
between 0 - 25%
▪ Output “1”: The current output of the HV module is
between 25 - 50%
▪ Output “2”: The current output of the HV module is
between 50 - 75%
▪ Output “3”: The current output of the HV module is
above 75%
Parameters overview
4
System
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en
97